Optional Module Installation
ANN-RLY Board Layout and Connection to FACP
Figure 2.29 illustrates the ANN-RLY board showing locations of screw terminals for connection to the FACP and the DIP switches for
selecting the ANN-BUS ID number.
2.8.4 Printer
A parallel printer may be connected to the FACP using the optional ANN-S/PG Serial/Parallel Interface Module. The printer can be used to
provide a hard-copy printout of real-time events, history file and walktest data. Installation of the device requires panel programming to
allow the FACP to communicate with the device. Refer to "ANN-S/PG Serial/Parallel Interface Module" on page 18 for installation details.
Refer to "ANN-BUS Setup" on page 87 for programming information.
CAUTION: POSSIBLE EQUIPMENT DAMAGE
!
DO NOT CONNECT A PRINTER OR PC TO THE ES-50X FACP IF A GROUND FAULT (ZERO IMPEDANCE TO GROUND)
EXISTS ON THE CONTROL PANEL. CIRCUIT DAMAGE MAY RESULT. REMOVE ALL POWER (PRIMARY AND
SECONDARY) BEFORE INSTALLING OR REMOVING ANY WIRING.

Printer Configuration

Refer to the documentation supplied with the printer for pertinent information about printer setup. Set the printer's options as listed in the
following table:
ES-50X Series Manual — P/N LS10129-000FL-E:D 4/26/2021
ANN-BUS (ID#)
Address DIP switch
ANN-BUS and power wiring are
supervised and power-limited
Figure 2.29 ANN-RLY Board Layout and Connection to FACP
COMMUNICATION SETUP
AUTOMATIC LINE FEED
AUTOMATIC CARRIAGE RETURN
TB2
TB4
TB5
TB3
TB6
ANN-BUS
TB1
+24 VDC
-24 VDC
Primary
ANN-BUS
+
-
ES-50X
BUFFER:
DATA BITS:
PARITY:
STOP BIT:
BAUD RATE:
Table 2.3 Printer Options
1 2 3 4 5 6 7 8
ANN-RLY
LARGE
7
EVEN
1 STOP
2400/4800/9600
NO
NO
Installation