3: Ann-Bus Annunciators/Modules; Ann-Bus Wiring - Honeywell Fire-Lite Alarms ES-50X Manual

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms ES-50X:
Table of Contents

Advertisement

Installation
NOTE: When a 4XTMF is installed, enable supervision in panel programming.
Jumper JS3 on the FACP main circuit board can be used to configure the FACP supervisory relay for operation with the 4XTMF module. Relay
3 at TB3 must be programmed as a supervisory relay.
Jumpering pins 2&3 on JS3 will allow the 4XTMF to generate a trouble if the supervisory contact opens.
Jumpering pins 1&2 on JS3 in will prevent generation of a trouble if the supervisory contact opens.
2.8.3 ANN-BUS Annunciators/Modules

ANN-BUS Wiring

This section contains information on calculating ANN-BUS wire distances and the types of wiring configurations (Class B).
Calculating Wiring Distance for ANN-BUS Modules
The following instructions will guide the installer in determining the type of wire and the maximum wiring distance that can be used with
FACP ANN-BUS accessory modules.
To calculate the wire gauge that must be used to connect ANN-BUS modules to the FACP, it is necessary to calculate the total worst case
current draw for all modules on a single 4-conductor bus. The total worst case current draw is calculated by adding the individual worst case
currents for each module. The individual worst case values are shown in the following table:
32
Standoff
J12 & J13 Connectors
4XTMF
Figure 2.16 4XTMF Connectors to ES-50X Connectors
Model Number
ANN-80 LCD Annunciator
ANN-100 LCD Annunciator
ANN-S/PG Serial/Parallel Printer Interface Module
ANN-I/O LED Driver Module
ANN-(R)LED Annunciator Module
ANN-RLY Relay Module
1 When powering the ANN-BUS from one of the (nonresettable) DC power outputs at TB11, the total
worst case current draw cannot exceed 1.0 amp. If sharing this DC output with other devices, the
worst case current drawn by these devices must be combined with the ANN-BUS current draw,
and the total cannot exceed 1.0 amp. If the total current demand exceeds 1.0 amp, refer to
"Powering ANN-BUS Devices from an Auxiliary Power Supply" on page 34.
ALRM
NO
NC
C
Jumper JS3
Standoff
FACP main circuit board
0.040 amps
0.025 amps
0.040 amps
0.200 amps
0.068 amps
0.075 amps
ES-50X Series Manual — P/N LS10129-000FL-E:D 4/26/2021
Optional Module Installation
TRBL
SUPV
RMT SYNC
NAC1
NO
NC
C
NO
NC
C
OUT+
RTN+
RTN- OUT-
1
2
3
1
Worst Case Current Draw

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fire-lite alarms es-50xc

Table of Contents