Honeywell Fire-Lite Alarms ES-50X Manual page 91

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms ES-50X:
Table of Contents

Advertisement

Master Programming Level
ANN-LED Options
ANN XXX
1=ENABLED
2=MODULES INSTALLED
3=AUTO-CONFIGURE
ANN-BUS XXX Screen #2
The first screen indicates that the ANN-LED at the selected ANN-BUS address is programmed to annunciate Alarms, Troubles and Supervi-
sories for Zones 000 through 009. The programming can be changed using ANN-LED Address Screen 2.
Pressing 1 while viewing ANN-LED Address Screen #2 will program the annunciator module to annunciate either Point (addressable device
address) information or Zone information. Each press of the 1 key will toggle the display between Point and Zone.
Pressing 2 while viewing ANN-LED Address Screen #2 will program the annunciator module to annunciate only Alarms or Alarms, Trou-
bles and Supervisories (ATS). Each press of the 2 key will toggle the display between Alarms and ATS.
Pressing 1 while viewing ANN-LED Address Screen #3 will select the Point or Zone range to be annunciated (refer to the tables in "ANN-
RLED Zone Option - Alarm Only" on page 91 and "ANN-RLED Point Option - Alarm Only" on page 92). Pressing the 1 key will display
an additional screen where the range can be selected.
If Zone has been selected, and Alarms Only are to be annunciated, he new screen will give the options of annunciating Zone 000 - 029
or 030 - 049. Two ANN-LED modules are required to annunciate all zones in this configuration.
If Zone has been selected, and Alarms, Troubles and Supervisories are to be annunciated, the new screen will give the options of
annunciating Zone 000 - 009, 010 - 019, 020 - 029, 030 - 039, or 040 - 049. Five ANN-LED modules are required to annunciate all
zones in this configuration.
If Points has been selected, and Alarms Only are to be annunciated, the new screen will give the options of annunciating Points 001 -
030 and 031 - 050. Two ANN-LED modules are required to annunciate all points in this configuration.
If Point has been selected, and Alarms, Troubles and Supervisories are to be annunciated, the new screens will give the options of
annunciating Points 001 - 010, 011 - 020, 021 - 030, 031 - 040 or 041 - 050. Five ANN-LED modules are required to annunciate all
points in this configuration.
ANN-RLED Zone Option - Alarm Only
If Zone is selected as the module option, and the module is programmed to annunciate alarms only, the first ten LEDs on the ANN-RLED
module will display the system status information. The remaining 30 LEDs on the first module and the last 30 LEDs on the second module
will display the active/alarm status of each zone in the Zone Range programmed for that particular module. The LED assignments for each
ANN-LED module will be as follows.
ES-50X Series Manual — P/N LS10129-000FL-E:D 4/26/2021
Pressing 2 for Module Options while viewing the ANN XXX Address Screen when the ANN-LED option is
selected, will display the following screens:
YES
ANN-LED - ADDR X-1
ZONES
000-009
ALARM, TRBL, SUPV
ANN-LED Address Screen #1
Alarm Silenced
NAC 1 Fault
Earth Fault
Battery Fault
Zone 000
Zone 001
Active/Alarm
Active/Alarm
Zone 005
Zone 006
Active/Alarm
Active/Alarm
Zone 010
Zone 011
Active/Alarm
Active/Alarm
Zone 015
Zone 016
Active/Alarm
Active/Alarm
Zone 020
Zone 021
Active/Alarm
Active/Alarm
Zone 025
Zone 026
Active/Alarm
Active/Alarm
Not Used
Not Used
Not Used
Not Used
Zone 030
Zone 031
Active/Alarm
Active/Alarm
Zone 035
Zone 036
Active/Alarm
Active/Alarm
Zone 040
Zone 041
Active/Alarm
Active/Alarm
Zone 045
Zone 046
Active/Alarm
Active/Alarm
Not Used
Not Used
Not Used
Not Used
ANN-LED - ADDR X-1
1=POINT/ZONE
2=ALARM/ATS
ANN-LED Address Screen #2
NAC 2 Fault
Charger Fault
Zone 002
Active/Alarm
Zone 007
Active/Alarm
Zone 012
Active/Alarm
Zone 017
Active/Alarm
Zone 022
Active/Alarm
Zone 027
Active/Alarm
Table 3.4 ANN-RLED Module #1
Not Used
Not Used
Zone 032
Active/Alarm
Zone 037
Active/Alarm
Zone 042
Active/Alarm
Zone 047
Active/Alarm
Not Used
Not Used
Table 3.5 ANN-RLED Module #2
ANN-LED - ADDR X-1
1=RANGE
ZONE
ATS
ANN-LED Address Screen #3
Not Used
Not Used
Disabled
Maintenance
Zone 003
Zone 004
Active/Alarm
Active/Alarm
Zone 008
Zone 009
Active/Alarm
Active/Alarm
Zone 013
Zone 014
Active/Alarm
Active/Alarm
Zone 018
Zone 019
Active Alarm
Active/Alarm
Zone 023
Zone 024
Active/Alarm
Active/Alarm
Zone 028
Zone 029
Active/Alarm
Active/Alarm
Not Used
Not Used
Not Used
Not Used
Zone 033
Zone 034
Active/Alarm
Active/Alarm
Zone 038
Zone 039
Active/Alarm
Active/Alarm
Zone 043
Zone 044
Active/Alarm
Active/Alarm
Zone 048
Zone 049
Active Alarm
Active/Alarm
Not Used
Not Used
Not Used
Not Used
Programming
ZN000-009
91