Programming
Silence Inhibit
NAC #
1=ZONE ASSIGNMENT
000
2=SILENC INHIBIT NO
NAC Screen #3
from 0-300 seconds. Pressing 2 while viewing NAC Screen #3 in Canadian mode only, will display the following:
A flashing cursor will appear in the lower left corner of the display. Type the three digit in suite silence delay in seconds (000 to 300 second
delay). The default time is 300 seconds. When the third digit is entered, the display will return to the NAC Screen #3 which will indicate the
new Silence Inhibit time.
Sync Type
NAC #
1=SYNC TYPE
NAC Screen #4
Pressing 1 while viewing this screen will select System Sensor synchronization, 2 will select Wheelock, and 3 will select Gentex.
Maximum Number of Strobes for Synchronization
The total current draw for each Notification Appliance Circuit cannot exceed 2.5 amps. Refer to the manufacturer's documentation supplied
with the Strobes to determine the maximum current draw for each strobe and ensure that the circuit maximum is not exceeded. To ensure
proper strobe and circuit operation, there is also a limit to the number of strobes that can be attached to each circuit.

Relays

SYSTEM SETUP
1=TIMERS
2=NACS
System Setup Screen #2
To program Relay 1 or Relay 3, press the number corresponding to the selected relay. Note that Relay 2 is fixed as a Trouble relay. Selecting
Relay 2 will have no effect on its programming. The following screen will appear for each relay to be programmed:
Pressing 1 for Type while viewing the Relay Screen will cause the following screens to be displayed:
RELAY
1=ALARM
2=SUPERVISORY
3=SUPERVISORY AR
Relay Screen #1
While viewing the selected screen, press the number corresponding to the desired relay type to program the main circuit board relay. The
choice will be stored in memory and the display will return to the Relay Type Screen which will show the programmed type choice. Press the
Escape key to return to the Relays Selection Screen and repeat the preceding procedure for the remaining relays.
NOTE:
1. AR (AutoResettable) in SUPERVISORY AR and PROCMON AR means that a relay with the Supervisory and/or Process Monitor type code,
when activated, will automatically reset when the corresponding condition is cleared.
2. A relay programmed with the Silenceable Alarm type will activate upon any alarm and deactivate when the FACP Alarm Silenced LED is
illuminated.
76
The Silence Inhibit feature, when enabled, prevents the silencing of the selected main circuit board NAC for a
period of five minutes. Resetting the FACP will also be prevented for the full duration of the silence inhibit
time. Pressing 2 while viewing NAC Screen #3 will cause the display to change from the factory default of
Silence Inhibit No to Silence Inhibit Yes. Each press of the 2 key will cause the display to toggle between the
two options. If the panel is set to Canadian mode of operation, the duration for Silence Inhibit is programmable
RANGE 0-300 SECONDS
If synchronized strobes were selected as the Type of device installed, the type of synchronization must be
S
selected in this option. Pressing 1 while viewing NAC Screen #4 will cause the following screen to be dis-
played:
1=SYSTEM SENSOR
2=WHEELOCK
3=GENTEX
Pressing 3 while viewing System Setup Screen #2 will allow the programmer to configure two main circuit
board Form-C relays from the following screen:
1=RELAY 1
2=RELAY 2
3=RELAY 3
1=TYPE
RELAY
1=TROUBLE
2=COMM FAIL
3=PROCESS_MON
Relay Screen #2
NAC SILENCE INHIBIT
NAC Silence Inhibit Screen
NAC SYNC TYPE
RELAYS
Relays Selection Screen
RELAY #
ALARM
Relay Type Screen
RELAY
1=PROCESS MON AR
2=AC LOSS
3=HAZARD
Relay Screen #3
ES-50X Series Manual — P/N LS10129-000FL-E:D 4/26/2021
Master Programming Level
RELAY
1=MEDICAL
2=SILENCEABLE ALARM
3=CARBON MONOXIDE
Relay Screen #4