Optional Module Installation
ANN-I/O Connection to FACP
The ANN-I/O connects to the FACP via the ANN-BUS as illustrated in Figure 2.23. After the ANN-I/O is connected to the panel, it must be
added to the system via FACP programming. Refer to the section titled "ANN-I/O Options" on page 88.
ANN-I/O Module LED Wiring
There are four 12-pin connectors on the ANN-I/O module for connecting LEDs. Each set of 10 LEDs get their power from Pin 11 of the cor-
responding connector. Internal resistors are sized so that there is approximately 10 mA of current for each LED. No series resistors are
required. LED outputs can be mapped to output circuits. Refer to the programming section titled "ANN-I/O Options" on page 88 of this
manual.
The LEDs are wired as illustrated in Figure 2.24. Note that the illustration depicts only connectors P1 and P2. Wiring is identical for P3
(LEDs 21-30) and P4 (LEDs 31-40).
ES-50X Series Manual — P/N LS10129-000FL-E:D 4/26/2021