5: System - Honeywell Fire-Lite Alarms ES-50X Manual

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms ES-50X:
Table of Contents

Advertisement

Maintenance Programming Level
3.6.5 System
PROGRAMMING
1=WALKTEST
2=SYSTEM
3=ZONE SETUP
Maintenance Screen #2
SYSTEM
1=NACS ENAB
2=REM SYNC ENAB
System Screen #1
Pressing 1 while viewing NAC Screen #1 will cause the display to change to NAC1 Yes. This will allow the selected main circuit board NAC
to activate its devices. Each press of the 1 key will cause the display to toggle between NAC1 Yes and NAC1 No. The same action is per-
formed for the other NAC circuit by selecting the number of the desired output circuit.
SYSTEM
1=NAC ENAB
2=REM SYNC ENAB
System Screen #1
To change the time, press 1 to display the following screen:
A flashing cursor will appear on the left side of the display. Enter the four digit number corresponding to the time (0000 - 1259). When the
fourth digit is entered, the cursor will move one position to the right. Press 1 for AM or 2 for PM to complete entering the time. The display
will return to the Time and Date Screen displaying the new time.
To change the date, press 2 while viewing the Time and Date Screen. The following screen will be displayed:
A flashing cursor will appear on the left side of the display. Enter the two digit month, two digit day and two digit year. The cursor will move
one position to the right after each entry. When the fourth digit of the year has been entered, the display will return to the Time and Date
Screen which will show the new date.
The clock can be configured to display 12 hour (AM & PM) or 24 hour (military) time. Pressing 3 while viewing the Time-Date screen will
cause the display to toggle between 12HR and 24HR. Select 12HR for 12 hour display or 24HR for 24 hour display.
SYSTEM
1=TIME/DATE
2=CHARGER ENAB
3=4XTM SPV ENAB
System Screen #2
there is a 4XTMF installed. Each press of the 1 key will cause the display to toggle between 4XTM Spv Enab. No and 4XTM Spv Enab. Yes.
ES-50X Series Manual — P/N LS10129-000FL-E:D 4/26/2021
Pressing 2 while viewing Maintenance Screen #2, will display the following screen:
SYSTEM
1=NACS ENAB
2=REM SYNC ENAB YES
System Screen #1
Pressing 2 while viewing System Screen #1 will display the following:
1,2
YES
1=NAC1
2=NAC2
To enable remote synchronization, press the 2 key while viewing System Screen #2. Each press of the key will
toggle the screen between Rem Sync Enab Yes and Rem Sync Enab No.
1,2
YES
Pressing 1 while viewing System Screen #2 will cause the following screen to be displayed:
1=TIME
2=DATE
3=CLOCK FORMAT 12HR
01:00 AM
1=AM
MONTH DAY YEAR
05-04-17
To enable the onboard battery charger, press the 2 key while viewing System Screen #2. Each press of the key
will toggle the screen between Charger Enab Yes and Charger Enab No. The setting must say Charger Enab No
NO
when an external battery charger is being used.
NO
If a 4XTMF Transmitter Module is installed in the system, supervision must enabled in user programming.
Pressing 3 while viewing System Screen #2 will cause the display to toggle to 4XTM Spv Enb. Yes, which means
1=TIME/DATE
1,2
2=CHARGER ENAB
3=4XTM SPV ENAB
ENABLE NACS
N
N
Enable NAC Screen
TIME AND DATE
01:00 AM
05-04-2017
Time and Date Screen
ENTER TIME
2=PM
Time Screen
ENTER DATE
Date Screen
SYSTEM
YES
NO
System Screen #2
Programming
101