Honeywell Fire-Lite Alarms ES-50X Manual page 88

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms ES-50X:
Table of Contents

Advertisement

Programming
Modules Installed
ANN XXX
1=ENABLED
2=MODULES INSTALLED
3=AUTO-CONFIGURE
ANN-BUS (XXX) Screen #1
Pressing the down arrow key will allow the programmer to view additional screens displaying Addresses 1-8. To select one or more
addresses for the installed module(s), press the number key corresponding to the module address in each screen. The following screen will
be displayed for each address:
Pressing 1 for Type will display the following screens:
ANN-BUS MODULE TYPE
1=NOT INSTALLED
2=ANN-80 MODULE
3=ANN-100 MODULE
Press the number corresponding to the module/device type that is installed with the selected address.
NOTE: If the module type selected is the ANN-80, ANN-100, or ANN-S/PG, or if Not Installed is selected, the ANN-BUS Address Screen
shown on the previous page will be displayed following the module selection. The options selected for each of these modules will be the same
for all modules of the same type (refer to "ANN-S/PG (Print) Options" on page 95 and "ANN-80/100 Options" on page 95).
If ANN-I/O, ANN-LED, or ANN-RLY is the selected module type, the following ANN-BUS Address Screen will be displayed:
Since the options for each of these module types can be individually set, pressing 2 for Module Options, while viewing the ANN-BUS
Address Screen will display the available options as described below.
ANN-I/O Options
Pressing 2 for Module Options while viewing ANN-BUS Address screen when the ANN-I/O option is selected will display the following
screen:
ANN-I/O - ADDR X-1
SLC 1 DET 001-030
ACTIVE LEDS ONLY
ANN-I/O Address Screen #1
Pressing 1 while viewing the ANN-I/O Address Screen #2 will program the annunciator module to annunciate either Point (addressable
device address) information or Zone information. Each press of the 1 key will toggle the display between Zone and Point.
Pressing 1 while viewing the ANN-I/O Address Screen #3 will select the Point range to be annunciated (refer to the tables in "ANN-I/O
Zone Option" on page 89 and "ANN-I/O Point Option" on page 90). If Point has been selected, each press of the 2 key for Range will
change the points to be annunciated with the options being 001 - 030 and 031 - 050.
Pressing 2 while viewing ANN-I/O Address Screen #3 will select either addressable detectors or addressable modules to be annunciated.
88
If an ANN-BUS module is installed, press 2 for Modules Installed to select ANN-BUS addresses for the mod-
ule(s). The only difference between the two programming screens are the addresses. The Primary Bus module
NO
addresses will have a prefix of "1-" while the Secondary Bus module addresses will have a prefix of "2-". The
following screen will be displayed for either bus circuit.
Module Type Screen #1
ANN-BUS MODULES
1=ADDR. X-1
NONE
2=ADDR. X-2
NONE
3=ADDR. X-3
NONE
ANN-BUS Modules Screen #1
ANN-BUS MODULE X-1
ANN-BUS ADDRESS
1=TYPE
NONE
ANN-BUS Address Screen
ANN-BUS MODULE TYPE
1=ANN-I/O MODULE
2=ANN-S/PG MODULE
3=ANN-LED MODULE
Module Type Screen #2
ANN-BUS MODULE X-1
ANN-BUS ADDRESS
1=TYPE
ANN-I/O
2=MODULE OPTIONS
ANN-BUS Address Screen
ANN-I/O - ADDR X-1
1=POINT/ZONE
POINT
ANN-I/O Address Screen #2
ES-50X Series Manual — P/N LS10129-000FL-E:D 4/26/2021
Master Programming Level
ANN-BUS MODULE TYPE
1=ANN-RLY MODULE
Module Type Screen #3
ANN-I/O - ADDR X-1
1=RANGE
PT001-030
2=DET/MOD
DET
ANN-I/O Address Screen #3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fire-lite alarms es-50xc

Table of Contents