Maintenance Programming Level; 1: Disable Point - Honeywell Fire-Lite Alarms ES-50X Manual

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms ES-50X:
Table of Contents

Advertisement

Programming
The Zone No Output feature allows the programmer to view the zones which have not been programmed to at least one output device (not
including general alarm Zone 00). The example in the preceding screen indicates that Zones 05, 07, 09, 10 and 11 have been programmed to
an addressable detector with an address of 001 on loop 1 but have not been programmed to any output devices. Use the up and down arrow
keys to view all the zones without output assignments.

3.6 Maintenance Programming Level

To access Maintenance Programming mode, press the Enter key. The LCD will display the following:
To enter the Maintenance Programming mode, press 2. The display will read as follows:
When the Maintenance level password (default 11111111) is entered, the following screen will appear:
Note that in the preceding screens, an arrow appears to inform the programmer that additional options can be viewed by pressing the keypad
down arrow key, as shown in the following screen.
3.6.1 Disable Point
MAINT PROGRAMMING
1=POINT PROGRAM
2=HISTORY
3=PROGRAM CHECK
Maintenance Screen #1
Select the device type by pressing 1 for an addressable detector or 2 for an addressable module. The operator will be prompted to enter the
three digit device address as shown in the following example for a detector:
A flashing cursor will appear in the bottom left corner of the display, prompting for the three digit device address. When the third digit is
enter, 001 for example, a screen will appear which will allow enabling or disabling of the selected point, as illustrated in the following exam-
ple:
Pressing 1 repeatedly will cause the display to toggle between Enabled Yes and Enabled No.
98
1=READ STATUS MODE
2=PROGRAMMING MODE
3=FSTOOL UP/DOWNLOAD
4=USB UP/DOWNLOAD
PROGRAMMING
ENTER PASSWORD
MAINT PROGRAMMING
1=POINT PROGRAM
2=HISTORY
3=PROGRAM CHECK
PROGRAMMING
1=WALKTEST
2=SYSTEM
3=ZONE SETUP
Pressing 1 for Point Program, while viewing Maintenance Screen #1 will cause the following screens to be dis-
played:
POINT PROGRAM
1=DETECTOR
2=MODULE
Device Select Screen
EDIT DETECTOR
ENTER POINT ADDRESS
Address Select Screen
EDIT DETECTOR 1D001
1=ENABLED
Enable/Disable Select Screen
YES
ES-50X Series Manual — P/N LS10129-000FL-E:D 4/26/2021
Maintenance Programming Level

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fire-lite alarms es-50xc

Table of Contents