Master Programming Level; 1=Autoprogram; 2=Point Program - Honeywell Fire-Lite Alarms ES-50X Manual

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms ES-50X:
Table of Contents

Advertisement

Programming

3.5 Master Programming Level

When the Master Program Level password is entered, the control panel will enter user Programming mode. In this mode, the piezo sounder
remains off, the trouble relay is activated and the system Trouble LED flashes until Programming mode is exited. The following display will
appear:
Pressing the down arrow will display more programming options:
1=LOOP SETUP
2=SYSTEM SETUP
3=FUTURE USE
Programming Screen #2
3.5.1 Autoprogram
PROGRAMMING

1=AUTOPROGRAM

2=POINT PROGRAM

3=ZONE SETUP
Programming Screen #1
newly installed devices.
When Autoprogram is selected, the control panel will begin autoprogramming the system by communicating with each addressable device
installed on the SLC loop. While autoprogramming, the panel will display the following:
When Autoprogramming is completed, the control panel will display the type and quantity of each device installed on the SLC loop similar
to the following display:
In the preceding example, the display indicates that the SLC Loop has 55 addressable detectors, 35 monitor modules and 30 control modules
installed.
Pressing the ESC key will return the display to Programming Screen #1.
3.5.2 Point Program
PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
Programming Screen #1
50
PROGRAMMING
Pressing 1 while viewing Programming Screen #1, will select the Autoprogram option, which prompts the con-
trol panel to poll all devices installed on the SLC loop. The primary purpose of autoprogramming is to allow the
installer a fast and easy way to bring the system on-line as quickly as possible. The first time the system is pow-
ered-up, it should be autoprogrammed.
If the system is already programmed and Autoprogram is initiated, the system will only add default values for
The Point Program option allows the programmer to add a new addressable device to the SLC loop, delete an
existing device from the loop or change the programming for an existing device. Pressing 2, while viewing
Programming Screen #1, will select the Point Program option and display the following screens:
PROGRAMMING
1=AUTOPROGRAM
2=POINT SETUP
3=ZONE SETUP
Programming Screen #1
PROGRAMMING
1=HISTORY
2=COMMUNICATOR
3=ANNUNCIATORS
Programming Screen #3
AUTOPROGRAM
AUTOPROGRAMMING!
PLEASE WAIT
Autoprogram Progress Screen
# OF DET LOOP1 055
# OF MON LOOP1 035
# OF CON LOOP1 030
Autoprogram Result Screen #1
POINT PROGRAM
SELECT TYPE
1=DETECTOR
2=MODULE
Point Program Screen
ES-50X Series Manual — P/N LS10129-000FL-E:D 4/26/2021
Master Programming Level
PROGRAMMING
1=PASSWORD CHANGE
2=CLEAR PROGRAM
3=PROGRAM CHECK
Programming Screen #4