Accessories
FS-Tools also provides the ability to create panel program files on a USB flash drive. The drive can then be plugged into USB port J20 on the
FACP main circuit board.
Important: Remote modification of FACP programming requires that the panel be enabled for remote download (refer to "FS-Tools
Upload/Download" on page 120). Remote interrogation of panel programming, history logs, detector status, etc., is possible without
enabling the remote download option.
1.6.2 Dress Panel
An optional dress panel, DP-ES-R is available for the ES-50X (required by ULC for Canadian installations). The dress panel restricts access
to the system wiring while allowing access to the key panel. A ground strap must be connected between the stud on the inside of the dress
panel and the ground stud in the backbox. The dress panel mounts to the backbox with two (2) #4 screws and washers or two (2) #6 screws.
The ES-50XC is supplied standard with a dress panel.
1.6.3 Trim Ring
An optional Trim Ring (P/N TR-CE) is available for the FACP backbox. The Trim Ring adds 1.5" of wall coverage around the backbox, con-
cealing hardware and providing a finished appearance for a semi-flush mounted panel.
1.6.4 Battery Box
BB-26
The BB-26 battery box may be used to house up to two 26 AH batteries and the CHG-75 Battery Charger.
BB-55F
The BB-55F battery box may be used to house two 26 AH batteries, two 60 AH batteries or one 100 AH battery. When the CHG-120F is
mounted in the BB-55F, two 26 AH or one 60 AH battery may also be housed in the battery box.
1.6.5 Battery Charger
CHG-75 Battery Charger
The CHG-75 is capable of charging up to 75 AH lead-acid batteries with the ES-50X FACP. The FACP battery charger must be disabled,
through user programming, when using the CHG-75. The charger and up to 26 AH batteries can be housed in the BB-26 battery box. Larger
batteries and the charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel. Refer to
the CHG-75 Manual for additional information.

CHG-120F Battery Charger

The CHG-120F is capable of charging up to 120 AH lead-acid batteries with the ES-50X FACP. The FACP battery charger must be disabled,
through user programming, when using the CHG-120F. The batteries and charger can be housed in the BB-55F battery box which can be
mounted up to 20 feet away from the control panel. Note that when using the BB-55F for housing the charger and batteries greater than
26AH, multiple BB-55Fs are required. Refer to the CHG-120F Manual for additional information.
1.6.6 W-GATE Wireless Gateway
The W-GATE Wireless Gateway acts as a bridge between a group of wireless fire devices and a LiteSpeed SLC loop on the ES-50X. It is
powered by the SLC loop or by a regulated, external 24VDC UL-listed power supply evaluated for life safety. Available wireless devices
include a photo detector, a photo/heat detector, a fixed-temperature heat detector, a rate-of-rise heat detector, a monitor module, and a relay
module. For details about wireless devices, system setup, and operation, see the SWIFT® Smart Wireless Integrated Fire Technology Instruc-
tion Manual #LS10036-000FL-E.
NOTE: The W-GATE, as part of the wireless network, has been tested for compliance with the Federal Communications Commission (FCC)
requirements of the United States Government. It has not been evaluated for use outside the USA. Use of this system outside the USA is
subject to local laws and rules to which this product may not conform. It is the sole responsibility of the user to determine if this product may be
legally used outside the USA.
ES-50X Series Manual — P/N LS10129-000FL-E:D 4/26/2021
Product Description
17

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fire-lite alarms es-50xc

Table of Contents