4: Ann-S/Pg Serial/Parallel Printer Interface Installation; Specifications; Printer Installation - Honeywell FIRE-LITE MS-10UD Series Manual

Fire alarm control panels
Hide thumbs Also See for FIRE-LITE MS-10UD Series:
Table of Contents

Advertisement

ANN-BUS Devices
Programming
Following installation and wiring of the ANN-80 LCD annunciator to the FACP, the annunciator must be added to the system via FACP
programming. Refer to the programming section titled "ANN-BUS" on page 71 in this manual for detailed programming information.
Select the LCD option for programming.
2.8.4 ANN-S/PG Serial/Parallel Printer Interface Installation
The ANN-S/PG Serial/Parallel Printer Interface module allows the ancillary connection of a serial or parallel printer to the FACP for a
real-time log of system events, detector status reports and event history. Proceed with the installation as described in the following:
1.
Ensure that all power (AC and DC) has been removed from the FACP.
2.
Connect the ANN-S/PG to the FACP as illustrated in Figure 2.23.
ANN-BUS and power wiring are
supervised and power-limited
3.
Using the DIP switches on the back of the ANN-S/PG module, assign an ID number (address) to the module.
4.
Select the address and configuration options for the ANN-S/PG module as described in the Programming section of this manual
(refer to"ANN-BUS" on page 71).
Note that the Auto-configure feature allows the programmer to quickly bring all installed ANN-BUS modules online (refer
to"Auto-Configure" on page 72).
5.
Connect a printer to the ANN-S/PG Parallel and/or Serial connectors (refer to Figure 2.23 on page 41).

Specifications

Operating Voltage: 24 VDC
Current (Alarm and Standby): 45 mA
Ambient Temperature: 32
Max. Wiring Distance from FACP: 6,000 ft. (1,800 m)
Mounting: Surface
Dimensions: 6"W x 7-3/4"H x 1-7/16"D (15.2 cm W x 19.7 cm H x 3.7 cm D)
For indoor use in a dry location only
PRN-7 Printer Installation
When connected to the FACP via the ANN-S/PG module, the PRN-7 prints the status changes within the control panel and time-stamps
the printout with the time of day and date that the event occurred. It provides 80 columns of data on standard 9" x 11" tractor-feed paper.
This section contains information on connecting a printer to the control panel and setting the printer options.
Connecting a PRN-7 Printer
Remote printers require a primary AC power source. If required for the fire alarm system configuration (for example, a Proprietary Fire
Alarm System), a remote printer requires a secondary power source (battery backup). Since a secondary power source is not provided as
a standard feature, a separate UL-listed Uninterruptible Power Supply (UPS) should be used. The building emergency power supply may
be used, as long as it meets the power continuity requirements of NFPA 72. Refer to NFPA 72 for further details.
Connect the remote printer to the FACP via the ANN-S/PG module using a standard DB-9 cable. One end of the cable will plug into the
DB-9 connector on the PRN-7 printer and the other end plugs into the serial connector on the ANN-S/PG module.
Setting Printer Options
Refer to the documentation supplied with the PRN-7 printer for instructions on using the printer menu controls. Set the printer options
(under the menu area) as shown in the following table:
MS-5UD & MS-10UD Series Manual — P/N 52626:C7 6/12/2018
TB3
Primary ANN-BUS
Figure 2.23 ANN-S/PG Connection to FACP
o
o
o
F to 120
F (0
C to 49
Primary ANN-BUS
ANN-S/PG Module
Cable Connectors for
connection to printer
o
C)
Parallel
(Use only one)
Serial
Installation
41

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents