Master Programming Level
Enable/Disable Detector
EDIT DETECTOR
1=ENABLED
2=TYPE
3=VERIFICATION
Edit Detector Screen #2
Type
To select the type of detector being programmed, press the 2 key while viewing the Edit Detector Screen #2.
This will cause the control panel to display the following Detector Type Screens:
DETECTOR TYPE
1=SMOKE(PHOTO)
2=USER-DEFINED-1
3=SMOKE(ION)
Pressing the down arrow key will display additional detector types as indicated in the following table.
While viewing either Detector Type screen, select the type of detector being programmed by pressing the corresponding keypad number key.
The display will return to Edit Detector Screen #2 and indicate the selection next to the Type option.
NOTE: If a detector is selected to be a DUCT SUPERV type, it will function like a supervisory point not a fire alarm point. The supervisory LED
and supervisory relay will activate, not the fire alarm LED or alarm relay, if the detector senses smoke.
If the selected detector is a multi-criteria Fire/CO detector, select 1 for Fire CO on the last screen and the following will display:
In this screen, select the action performed by the detector when it is activated. Press 1 to change the response for the Photo element of the
detector, 2 for the Heat element, and 3 for the CO element. The detector response will toggle between Alarm (sends an Alarm signal to the
FACP), Supervisory (sends a Supervisory signal to the FACP, and None (no signal sent to the FACP).
Verification
EDIT DETECTOR
1=ENABLED
2=TYPE
3=VERIFICATION
Edit Detector Screen #2
ES-50X Series Manual — P/N LS10129-000FL-E:D 4/26/2021
To Enable or Disable the detector, press the 1 key while viewing the Edit Detector Screen #2. Each press of the
key will toggle the screen between Enabled Yes and Enabled No. If Enabled No is selected, the detector will not
be polled by the control panel, preventing the detector from reporting alarms and troubles to the panel. The con-
trol panel will display the device type and address which has been disabled and will turn on the Trouble LED
and Disable LED.
through
Detector Type
Smoke Photo
User-Defined-1
Smoke (Ion)
User-Defined-2
Heat Detect
User-Defined-3
Smoke Duct-P
User-Defined-4
Photo w/Heat
User-Defined-5
Duct Superv
User-Defined-7
Photo Super AR
User-Defined-8
ADAPT
User-Defined-10
Beam
User-Defined-11
Fire/CO
User-Defined-12
1=CO
2=HEAT
3=PHOTO
Alarm verification is used to confirm that a smoke detector activation is a true alarm condition and not a false
alarm. This feature is selected by pressing 3 while viewing the Edit Detector Screen #2 so that the display reads
Verification On. Each time the 3 key is pressed, the display will toggle between Verification On and Verification
Off. For a detailed description, refer to "Alarm Verification (None or One Minute)" on page 110.
DETECTOR TYPE
1=FIRE CO
2=USER-DEFINED-12
Action When Activated
Fire Alarm
same as previous (Smoke Photo)
Fire Alarm
same as previous (Smoke Ion)
Fire Alarm
same as previous (Heat Detect)
Fire Alarm
same as previous (Smoke Duct-P)
Fire Alarm
same as previous (Photo w/Heat)
Supervisory, latching
same as previous (Duct Superv)
Supervisory, nonlatching (works only in LiteSpeed)
same as previous (Photo Super AR)
Fire Alarm
same as previous (ADAPT)
Fire Alarm
same as previous (Beam)
response is programmable (Alarm, Supv, or None)
same as previous (Fire/CO)
DETECTOR RESPONSE
ALARM
ALARM
ALARM
Programming
EDIT DETECTOR
1=ENABLED
2=TYPE
3=VERIFICATION
Edit Detector Screen #2
53