Master Programming Level
Clock Format
The clock can be configured to display 12 hour (AM & PM) or 24 hour (military) time. Pressing 3 while viewing the Time-Date screen will
cause the display to toggle between 12HR and 24HR. Select 12HR for 12 hour display or 24HR for 24 hour display.
NOTE: If the clock is changed to 24 hour (military) format, the date will change to the European standard of Day-Month-Year (for display
purposes only).
Daylight Savings Time
TIME AND DATE
1=DAYLIGHT SAVINGS
Time & Date Screen #2
Pressing 1 while viewing Daylight Savings Screen #1 will cause the display to toggle between Enabled Yes and Enabled No. The control
panel will automatically update the time for daylight savings time when Enabled Yes is selected.
Pressing 2 while viewing Daylight Savings Screen #1 will display another screen which allows the programmer to select the month that day-
light savings time will begin. In this sub-screen, pressing 1 will select March, 2 will select April, and 3 will select May.
Pressing 3 while viewing Daylight Savings Screen #1 will display two sub-screens which allow the programmer to select the week of the
month that daylight savings time will begin. In the first sub-screen, pressing 1 will select the first week, 2 will select the second week and 3
will select the third week, while in the second sub-screen, pressing 1 will select the fourth week and 2 will select the last week of the selected
month.
Pressing 1 while viewing Daylight Savings Screen #2 will display another screen which allows the programmer to select the month that day-
light savings time will end. In this sub-screen, pressing 1 will select September, 2 will select October, and 3 will select November.
Pressing 2 while viewing Daylight Savings Screen #2 will display two sub-screens which allow the programmer to select the week of the
month that daylight savings time will end. In the first sub-screen, pressing 1 will select the first week, 2 will select the second week and 3
will select the third week, while in the second sub-screen, pressing 4 will select the fourth week and 5 will select the last week of the selected
month.

Timers

SYSTEM SETUP
1=TIMERS
2=NAC
System Setup Screen #2
PAS (Positive Alarm Sequence) Delay
TIMERS
1=PAS DELAY
000
2=PRE SIGNAL
000
3=WATERFLOW
000
Timer Screen #1
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of three digits, such as 005 for five sec-
onds. Upon entering the third digit, the time delay will be stored in the control panel memory and the display will return to the Delay Screen
which will indicate the new delay time.
Pre-signal Delay
The factory default setting for Pre-signal delay is 000 for no delay. To select a Pre-signal delay of 001 to 180 seconds for all devices pro-
grammed for Pre-signal, press 2 while viewing Timer Screen #1. The following screen will be displayed:
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of three digits, such as 009 for nine sec-
onds. Upon entering the third digit, the time delay will be stored in the control panel memory and the display will return to the Delay Screen
which will indicate the new delay time.
ES-50X Series Manual — P/N LS10129-000FL-E:D 4/26/2021
Pressing 1 while viewing Time-Date Screen #2 will cause the following screens to be displayed:
DAYLIGHT SAVINGS
1=ENABLED
2=START MONTH
3=START WEEK
WEEK-2
Daylight Savings Screen #1
Timer delays for PAS, Pre-signal and waterflow activation can be programmed by pressing 1 while viewing
System Setup Screen #2. The following screen will be displayed:
TIMERS
1=PAS DELAY
000
2=PRE SIGNAL
000
3=WATERFLOW
000
Timer Screen #1
The factory default setting for PAS is 000 for no delay. To select a PAS delay of 001 to 180 seconds for all
devices programmed for PAS, press 1 while viewing Timer Screen #1. The following display will appear:
RANGE 0-180 SECONDS
PRESIGNAL DELAY
RANGE 0-180 SECONDS
Pre-signal Delay Screen
DAYLIGHT SAVINGS
1=END MONTH
YES
2=END WEEK
MAR
Daylight Savings Screen #2
TIMERS
1=AC LOSS DELAY
2=CTRL MOD DLY
3=CTRL AUTO SIL. 000
Timer Screen #2
PAS DELAY
PAS Delay Screen
NOV
WEEK-1
TIMERS
1=IN SUITE SIL.
2
2=SUITE RESOUND
000
Timer Screen #3