Appendix D: Wire Requirements - Honeywell Fire-Lite Alarms ES-50X Manual

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms ES-50X:
Table of Contents

Advertisement

T-tapping of the SLC loop wiring is allowed for 2-wire (Class B) configurations. The total resistance of any branch cannot exceed 40
ohms. The total wire length of all branches cannot exceed 10,000 feet (3,000 m).
Connecting external system accessories to the ES-50X main circuits must be carefully considered to ensure proper operation. It is
important to use the correct type of wire, gauge and run length for each ES-50X circuit. Reference the chart below to specify wire
requirements and limitations for each ES-50X circuit.
Note:
1.
If the SLC loop is to be run in conduit with Notification Appliance Circuits, the risk of encountering problems can be greatly
reduced by exclusively employing electronic sounders instead of more electronically noisy notification appliances such as
electromechanical bells or horns.
2.
The SLC can be programmed to operate in LiteSpeed mode (factory default setting) for a quicker device response time. While
shielded wire is not required in LiteSpeed mode, it is recommended that all SLC wiring be twisted-pair to minimize the effects of
electrical interference. Use the following table to determine the specific wiring requirements for the SLC when unshielded wire is
used:
Refer to Table D.1 on page 138 and Table D.2 on page 139 for wiring requirements.
CIRCUIT CONNECTIONS
Circuit Type
Circuit Function
Connects to
Addressable
Devices
CLIP MODE
SLC loop
(power-
limited)
LITESPEED
MODE
ANN-BUS
Connects to
(EIA-485)
annunciator
(power-
modules/
limited)
monitor
Initiating Device
module
Circuit: Contact
(power-
Closure
limited)
monitor
Initiating Device
module
Circuit: Two-wire
(power-
Modules
limited)
control
Notification
module
Appliance Circuit
(power-
limited)
Remote Sync
Provides strobe
Output
and normal sync
for remote NAC
power supplies
1 When using untwisted, unshielded wire, full conduit is recommended for optimum EMI/RFI protection.
138

Appendix D: Wire Requirements

Wire Type and
Limitations
Twisted, shielded pair
10,000 (3,000 m)
40 ohms maximum per
8,000 (2,400 m)
length of Class A loops. 40
4,875 (1,450 m)
ohms per branch maximum
3,225 (980 m)
for Class B loops
Twisted, unshielded pair
10,000 (3,000 m)
40 ohms maximum per
8,000 (2,400 m)
length of Class A loops. 40
4,875 (1,450 m)
ohms per branch maximum
3,225 (980 m)
for Class B loops
1
Untwisted, unshielded pair
3,000 (900 m)
Twisted pair
6,000 (1,800 m)
Maximum loop wire
resistance is 2 ohms for
power and 40 ohms for
data
Maximum loop wire
2,500 (760 m)
resistance is 1500 ohms
No more than a 2.4 volt
2,500 (760 m)
drop allowed at end of
circuit. Maximum loop wire
resistance is 25 ohms
In alarm, no more than a
Distance limitation set
1.2 volt drop allowed at end
by 1.2 volt maximum
of circuit
line drop
Untwisted, unshielded pair
Distance set by 295
wire
ohm resistance
limitation
Table D.1 FACP Wire Specifications
WIRE REQUIREMENTS
Recommended Max.
Distance
Wire Gauge and Compatible Brands
Feet (meters)
12 AWG (3.25 mm
Signal 98230, Belden 9583, WPW999
14 AWG (2.00 mm
Signal 98430, Belden 9581, WPW995
16 AWG (1.30 mm
Signal 98630, Belden 9575, WPW991
Direct Burial Cable Isotec NP713110VNQ-S
18 AWG (0.75 mm
Signal 98300, Belden 9574, WPW975
Direct Burial Cable Isotec NP714110VNQ-S
12 AWG (3.25 mm
6020UL, Genesis WG-4315 & WG-4515
14 AWG (2.00 mm
6120UL, Genesis WG-4313 & WG-4513
16 AWG (1.30 mm
6220UL, Genesis WG-4311 & WG-4511
18 AWG (0.75 mm
6320UL, Genesis WG-4306 & WG-4506
12-18 AWG (3.25 - 0.75 mm
Refer to "ANN-BUS Wiring" on page 32 for
information on device wiring
12-18 AWG (3.25 - 0.75 mm
12-18 AWG (3.25 - 0.75 mm
12-18 AWG (3.25 - 0.75 mm
12-18 AWG (3.25 - 0.75 mm
ES-50X Series Manual — P/N LS10129-000FL-E:D 4/26/2021
2
): Genesis 4410,
2
):Genesis 4408 & 4608
2
): Genesis 4406 & 4606
2
): Genesis 4402 & 4602
2
): Belden 5020UL &
2
):Belden 5120UL &
2
): Belden 5220UL &
2
): Belden 5320UL &
2
) using listed wire
2
)
2
)
2
)
2
)