Programming
Enable
To enable the phone line, press 1 while viewing the POTS Line (X) Screen #1 to change the display to Enabled Yes. Each press of the 1 key
will cause the display to toggle between Enabled Yes and Enabled No.
NOTE: For UL applications: when POTS is used as the primary transmission path, the use of POTS as the secondary transmission path is
only allowed with approval of the local AHJ.
For ULC applications: when POTS is used as the primary transmission path, alarm signals will be sent out on both the primary and secondary
transmission paths.
Account Code
POTS XXX COMM PATH
1=ENABLED
2=ACCT CODE
000000
POTS Comm Path Screen #1
The Account Code, which is assigned by a Central Station, depends on the communication format being used. The Account Code screen will
have a flashing cursor in the lower left corner. Enter the supplied account code using 0 - 9 and A- F keys.
Phone Number
POTS XXX COMM PATH
2=PHONE NUMBER
2035554321
POTS Comm Path Screen #2
The Phone Number screen is used to enter the Central Station phone number that the Communicator will be contacting. A maximum of 20
characters can be entered with valid entries being 0 - 9 and A - C where A = *, B = # and C = 2 seconds pause.
A flashing cursor will appear in the lower left corner of the screen. Enter the first digit then press the right arrow key to move the cursor to
the right one position. Enter the second digit and repeat the process until all digits are entered. Press the Enter key to store the phone number
in memory.
Communication Format
POTS XXX COMM PATH
1=COMM FORMAT
ADEMCO CONTACT ID
POTS Comm Path Screen #3
The Communication Format is determined by the type of receiver that the Communicator is transmitting to. Consult your Central Station for
proper selection or consult our factory representatives. For any format chosen, the control panel automatically programs all of the event
codes.
Select the Communication Format by pressing the corresponding number key while viewing the Comm Format screen. The following table
describes each format:
Test Time Interval
The test report sent to the Central Station phone number may be sent once every 1, 2, 3, 4, 6, 8, 12, or 24 hours. Pressing 1 while viewing
POTS (XXX) Comm Path #4 will toggle the available settings. Refer to the table on page 47 for permissible settings.
24 Hour Test Time
POTS XXX COMM PATH
1=TEST TIME INT
2=24HR TEST TIME 0100
POTS Comm Path Screen #4
82
Pressing 3 while viewing POTS (XXX) Path Screen #1 will cause the following screen to be displayed:
NO
Pressing 2 while viewing POTS XXX Path Screen #2 will cause the following screen to be displayed:
Pressing 1 while viewing Primary/Secondary Screen #3 will cause the following screen to be displayed:
1=ADEMCO CONTACT ID
2=SIA 8
3=SIA 20
Screen Selection
ADEMCO CONTACT ID
SIA 8
SIA 20
Table 3.2 Communication Formats
Pressing 2 while viewing POTS (XXX) Comm Path #4 will cause the following screen to be displayed:
24
ACCOUNT CODE
ENTER 6 DIGITS
Account Codes Screen
PHONE NUMBER
20 NUMBERS MAXIMUM
Phone Numbers Screen
COMM FORMAT
Communication Format Description
Contact ID, DTMF, 1400/2300 ACK
Security Industry Association, 8 messages per call
Security Industry Association, 20 messages per call
24 HOUR TEST TIME
RANGE 0000-2359
24 Hour Test Time Screen
ES-50X Series Manual — P/N LS10129-000FL-E:D 4/26/2021