Canadian Option; Waterflow Silenceable; Auxiliary Power - Honeywell Fire-Lite Alarms ES-50X Manual

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms ES-50X:
Table of Contents

Advertisement

Master Programming Level

Canadian Option

SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
System Setup Screen #3
Important! For Canadian Applications, this option must be set to ON prior to any other panel programming.
The Canadian Options configures the FACP with the following as required by Canada:
The following monitor module type codes are not available:
monitor
non-latching supervisory
non-latching drill
non-latching process monitor
process monitor
hazard
tornado
medical alert
The following features become available:
Sounder Base Auto Silence
Control Module Auto Silence
Special Zone 45 CO Active
Special Zone 44 In Suite Silence
Control Module Auto Silence Timer
In Suite Silence Timer
In Suite Resound Timer
Programmable NAC Silence Inhibit
ANN-Bus annunciator keys enable
Control modules are no longer associated with the auto silence setting for NAC 1.
Addressable ionization smoke detector sensitivity is automatically monitored using Canadian specifications.
The Positive Alarm Sequence and Pre-Signal option are not available for Canadian applications.
The F1 function key is automatically configured to perform a manual alarm signal activation when pressed.
The F2 function key is automatically configured to perform an automatic alarm signal cancel in two-stage NAC operation when
pressed. This prevents the NAC from advancing to the second-stage alarm.
The F3 function key is automatically configured to force active two-stage NACs into the second (alarm) stage.
If NACs are set up for two-stage operation, the Silence Inhibit timer is automatically enabled and is fixed at 5 minutes.
AlarmNet supervision settings are fixed at 3 minutes and cannot be changed regardless of supervision programming selection.

Waterflow Silenceable

SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
System Setup Screen #3

Auxiliary Power

SYSTEM SETUP
1=AUX POWER
2=TROUBLE REM
3=LANGUAGE
ENGLISH
System Setup Screen #4
Select the AUX 1 output. The following screen will be displayed.
Aux 1 can be programmed for Class A wiring. If Aux 1 is to be wired for Class A, press 1. Each press of the 1 key will cause the display to
toggle between Class A Yes and Class A No.
ES-50X Series Manual — P/N LS10129-000FL-E:D 4/26/2021
Pressing 1 while viewing System Setup Screen #3 will configure the FACP to comply with Canadian require-
ments. The display will change to Canadian Opt. On. Each press of the 1 key will cause the display to toggle
between Canadian Opt. On and Canadian Opt. Off. Refer to the table on page 47 for permissible settings.
Pressing 2 while viewing System Setup Screen #3 will allow the programmer to configure the system for
silenceable on nonsilenceable waterflow circuits. Each press of the 2 key will toggle the display between Water-
flow Sil. No and Waterflow Sil. Yes. When Waterflow Sil. No is selected, all output devices associated with a
waterflow type input device, will be nonsilenceable. When Waterflow Sil. Yes is selected, all output devices
associated with a waterflow type input device, will be silenceable.
A Special Application 24 VDC power output is available at TB11 on the main circuit board. Pressing 1 while
viewing System Setup Screen #4 displays the following:
24HR
SYSTEM SETUP
1=CANADIAN OPT
OFF
2=WATERFLOW SIL. NO
AUX POWER
1=AUX 1
AUX 1
1=CLASS A
YES
2=RESETTABLE
YES
Programming
77

Advertisement