Programming
Note that the FACP allows programming for PAS and Pre-signal timers, but a detector can only be programmed for either PAS or Pre-signal
operation. Refer to"Edit Detector" on page 52 for programming details.
Waterflow Delay
TIMER
1=PAS DELAY
000
2=PRE SIGNAL
000
3=WATERFLOW
000
Timer Screen #1
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of two digits, such as 25 for twenty-five
seconds. Upon entering the second digit, the time delay will be stored in the control panel memory and the display will return to the Delay
Screen which will indicate the new delay time.
AC Loss Delay
TIMER
1=AC LOSS DELAY
2=CTRL MOD DLY
3=CTRL AUTO SIL. 000
Timer Screen #2
Pressing 1 while viewing AC Loss Delay Screen #1 will program the FACP to transmit an AC Loss report immediately to the central station.
Pressing 2 while viewing AC Loss Delay Screen #1 will display the following:
A flashing cursor will appear in the lower left corner of the display. Type the two digit AC loss reporting delay in hours (00 to 23 hour
delay). When the second digit is entered, the display will return to AC Loss Delay Screen #1. Refer to the table on page 47 for permissible
settings.
NOTE: Upon the loss of AC power at the control panel, relays programmed for 'AC Loss' will transfer immediately, regardless of the AC Loss
Delay setting. If no trouble exists at the panel other than AC Loss, the System Trouble relay will delay its activation for the duration of the AC
Loss Delay setting.
Control Module Delay
TIMER
1=AC LOSS DELAY
2=CTRL MOD DLY
3=CTRL AUTO SIL.
Timer Screen #2
A flashing cursor will appear in the lower left corner of the display. Type the three digit control module delay in seconds (000 to 180 second
delay). When the third digit is entered, the display will return to the Delay Screen which will indicate the new delay time. Refer to the table
on page 47 for permissible settings.
72
A delay can be added prior to declaring a waterflow type of alarm. Be careful to include any built-in delays of
the waterflow device. The factory default setting for Waterflow delay is 000 for no delay. To select a Waterflow
delay of 01 to 90 seconds for all devices programmed for Waterflow delay, press 3 while viewing Timer Screen
#1. The following screen will be displayed:
WATERFLOW DELAY
RANGE 0-90 SECONDS
Waterflow Delay Screen
The reporting of a loss of AC power to a central station can be delayed by programming the length of the
desired delay. The factory default setting is 2 hours. Press 1 while viewing Timer Screen #2 to display the fol-
lowing:
AC LOSS DELAY
1=NO DELAY
2=ENTER DELAY
AC Loss Delay Screen #1
AC LOSS DELAY
RANGE 00-23
AC Loss Delay Screen #2
The control module delay feature, if enabled, will delay activation of a control module after being triggered by
an alarm condition. Pressing 2 while viewing Timer Screen #2 will display the following:
CTRL MOD DELAY
RANGE 0-180 SECONDS
Control Module Delay Screen