Master Programming Level
Pre-signal
EDIT MONITOR
1=PRE-SIGNAL
WIRELESS
NO
Edit Monitor Screen #3
Wireless
EDIT MONITOR
1=PRE-SIGNAL
WIRELESS
Edit Monitor Screen #3
Walktest
EDIT MONITOR
1=WALKTEST
2=ZONE ASSIGNMENT
000
Edit Monitor Screen #4
Zone Assignment
A maximum of five zones can be programmed to each addressable monitor module. Pressing 2 while viewing Edit Monitor Screen #4 dis-
plays the following screen:
Note that Z*** represents the Zone Number(s) corresponding to this device. The factory default for an unprogrammed device is Z000 for
general alarm zone. A flashing cursor will appear on the first 0 to the left. Enter the three digit number corresponding to the zone that is to be
assigned to this device. The cursor moves to the next Z*** designation. Continue entering zone assignments or the remaining zones can be
left blank or programmed as general alarm zones Z00. When all desired changes have been made, press the Enter key to store the zone
assignments. The display will return to the Edit Monitor Screen #4.
Noun/Adjective
EDIT MONITOR
1=NOUN/ADJECTIVE
2=DESCRIPTION
Edit Monitor Screen #5
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Noun/Adjective Screen
1=NORTH
2=SOUTH
3=EAST
Adjective Screen #1
1=3RD
2=4TH
3=5TH
Adjective Screen #5
ES-50X Series Manual — P/N LS10129-000FL-E:D 4/26/2021
To enable the Pre-signal feature, press 1 while viewing Edit Monitor Screen #3 until the display reads Pre-signal
Yes. Each press of the 1 key will cause the display to toggle between Pre-signal Yes and Pre-signal No. Refer
NO
to"Presignal" on page 109 for additional information.
The Wireless selection will update automatically if the system recognizes a wireless device. If the module is
NO
wireless, the display reads Wireless Yes. If the module is wired, the display will read Wireless No. Fore more
NO
information on the SWIFT wireless network, refer to the SWIFT manual, #LS10036-000FL-E.
The Walktest feature allows one person to test the system devices without the necessity of manually resetting the
control panel after each device activation. To enable devices, which are connected to a monitor module, for the
Walktest feature, press 1 while viewing the Edit Monitor Screen #4 until the display reads Walktest Yes. Each
press of the 1 key will cause the display to toggle between Walktest Yes and Walktest No. Refer to "Walktest" on
page 110 for additional information.
The Noun/Adjective selection allows the programmer to enter specific descriptors about the monitor module
currently being programmed. Pressing 1 while viewing Edit Monitor Screen #5 will cause the following screen
to be displayed:
Pressing 1 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note
that the keypad down arrow key must be pressed to see all the Adjective screens. Press the number correspond-
ing to the adjective that is to be used as a descriptor for the location of the monitor module currently being pro-
grammed.
1=WEST
2=FRONT
3=CENTER
Adjective Screen #2
1=FLOOR 1
2=FLOOR 2
3=FLOOR 3
Adjective Screen #6
ZONE ASSIGNMENT
Z000 Z
Z
Z
Z
Zone Assignment Screen
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Noun/Adjective Screen
1=REAR
2=UPPER
3=LOWER
Adjective Screen #3
1=FLOOR 4
2=FLOOR 5
3=ROOM
Adjective Screen #7
Programming
1=MAIN
2=FIRST
3=2ND
Adjective Screen #4