4: Loop Setup; Class; Loop Protocol; Device Addressing - Honeywell Fire-Lite Alarms ES-50X Manual

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms ES-50X:
Table of Contents

Advertisement

Programming
3.5.4 Loop Setup
PROGRAMMING
1=LOOP SETUP
2=SYSTEM SETUP
3=FUTURE USE
Programming Screen #2

Class

To program the SLC Class for the selected loop, press 1 for Class, while viewing Loop Setup Screen. In the preceding example, the control
panel is programmed for Class B SLC wiring as indicated by the B to the right of Class in the display. To change the wiring style, press 1 to
toggle the display to read Class A. Each press of the 1 key will cause the display to toggle between Class B and Class A.
NOTE: If the FACP reports an open fault on an SLC Loop programmed for Class A, the trouble condition will latch at the FACP. When the SLC
Loop has been repaired, the Reset button must be pressed at the FACP (at least 2 minutes after the trouble has been repaired) to clear the SLC
trouble.

Loop Protocol

Loop Protocol refers to the SLC loop mode of operation. Refer to "Wire Requirements" on page 138 for wire specifications based upon SLC
protocol. There are two Loop Protocols available:
CLIP (Classic Loop Interface Protocol) - which is used for the older legacy addressable devices such as the M300 Series modules and
detectors.
LiteSpeed (factory default setting) - used for the 350 Series or newer addressable devices for quicker response times. Note that the
legacy devices can operate only in CLIP mode while the newer devices are compatible with CLIP and LiteSpeed modes of operation.
Pressing 2 while viewing the Loop Setup Screen will toggle between CLIP and LiteSpeed Protocols.

Device Addressing

It is important to note that the ES-50X addressable device capacity is 50 detectors and control/ monitor modules. Addressable devices must
not be set to addresses higher than 50. Programming will not allow addresses higher than 50.
Note that it is permissible to mix old and new devices on the same loop but the FACP must be set for CLIP mode when older devices are
installed.
3.5.5 System Setup
System Setup allows the programmer to configure the following control panel features:
Function Keys: This feature allows the user to rapidly enable/disable various fire panel inputs and outputs during scheduled
maintenance.
Banner: This option allows the user to change the top two lines of the LCD display from the blank factory default readout to a user
defined readout when the control panel is in Normal condition.
Time-Date: This feature allows the programmer to set the time, display format (24 hr or 12 hr), date and daylight savings time feature
into the FACP memory
Timers: This option allows the programmer to set the PAS (Positive Alarm Sequence) time delay, Pre-Signal time delay and Waterflow
time delay.
NACs: This feature allows the programmer to configure the control panel Notification Appliance Circuits for a variety of options, such
as circuit type, silenceable/nonsilenceable, autosilence, coding, silence inhibit, zone assignment and enable/disable.
Relays: This option allows programming of two onboard relays for activation by various control panel events, such as alarm, trouble,
supervisory, etc.
Canadian Option: This option allows the programming of certain options to Canadian specifications.
Waterflow Silenceable: This option provides the ability to silence any output circuit activated by a monitor module programmed as a
waterflow type.
Auxiliary Power: This option configures the use of the 24VDC auxiliary power output at TB11 on the FACP.
Trouble Reminder: This feature provides an audible reminder that an alarm or trouble still exists on the FACP after the control panel has
been silenced. The control panel piezo sounder will pulse once every 15 seconds during an alarm and every two minutes during a
trouble condition, after the Alarm Silence or Acknowledge key is pressed. The piezo will continue to sound at these rates until the alarm
or trouble condition is cleared. If the trouble condition is not cleared within a selected time of either 4 or 24 hours, the panel will
reactivate the trouble sounder and retransmit the trouble condition to the central station if connected. When used with SWIFT wireless
devices, the Trouble Reminder must be set to 4 hours.
Language: This option allows the user to switch between English and French language text on the panel display.
Charger Enable: This option allows the user to install an external battery charger.
4XTM Supervision: This feature enables supervision of an installed 4XTMF Transmitter Module.
Remote Sync Enable: This feature controls the activation of notification appliances in such a way that all devices will turn on and off at
exactly the same time.
68
Loop Setup allows the programmer to configure the SLC Loop for NFPA Class A or B wiring and to select the
loop protocol. Pressing 1 while viewing Programming Screen #2 will cause the following screen to be dis-
played:
1=CLASS
2=PROTOCOL LITESPEED
LOOP SETUP
B
Loop Setup Screen
ES-50X Series Manual — P/N LS10129-000FL-E:D 4/26/2021
Master Programming Level

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fire-lite alarms es-50xc

Table of Contents