Installation
Figure 2.18 illustrates the wiring between the FACP's Secondary ANN-BUS and ANN-BUS devices.
Powering Both ANN-BUS Circuits Simultaneously
When simultaneously using the Primary and Secondary ANN-BUS circuits on the FACP, power can be shared from the Nonresettable Power
output on TB11. Alternately, one ANN-BUS can be powered by the Resettable Power output (TB11 Terminals 3 and 4) once it is reconfig-
ured as Nonresettable Power in panel programming. This provides the benefit of independently acting power-limiting for the two ANN-BUS
circuits (required for Canadian applications).
Powering ANN-BUS Devices from an Auxiliary Power Supply
Figure 2.19 illustrates the powering of ANN-BUS devices from an auxiliary power supply such as the FCPS-24FS6/8, when the total ANN-
BUS power requirements exceed the panel's DC Power Output capability.
SW1
34
ANN-BUS and power wiring are
supervised and power-limited
TB1
4 3 2 1
ANN-BUS Device
Figure 2.18 Secondary ANN-BUS wiring to ANN-BUS Device
OUT4
OUT3
OUT2
OUT1
- NAC4 +
- NAC3 +
- NAC2 +
- NAC1 +
TB2
AUX TBL
NO
NC
COM
8
7
6
5
4
3
2
1
3
2
1
JP1
J3
JP3
AUX -
10
9
AUX +
8
IN2-
7
IN2+
6
OUT1-
5
OUT1+
4
IN1-
3
IN1+
2
SYNC IN -
1
SYNC IN +
ON
1 2 3 4 5 6 7 8
TB4
FCPS-24FS6/8
Figure 2.19 Powering ANN-BUS Devices from FCPS-24FS6/8
Secondary
ANN-BUS
Cut Ground Fault Detection jumper JP1
(FACP monitors for ground faults).
ANN-BUS and power wiring are
supervised and power-limited
TB5
-24 VDC
+24 VDC nonresettable
JP2
Primary
ANN-BUS
ES-50X
ES-50X Series Manual — P/N LS10129-000FL-E:D 4/26/2021