Table 3-2. Ups Cabinet Clearances; Table 3-3. 93E Required Clearance - Eaton 93E UPS Installation And Operation Manual

15–80 kva (380/400/415v)
Table of Contents

Advertisement

The UPS cabinet uses forced air cooling to regulate internal component temperature. Air inlets are in the front
of the cabinet and outlets are in the back of the cabinet. Allow clearance in front of and in back of the cabinet
for proper air circulation. The clearances required around the UPS cabinet are shown in Table 3-2.

Table 3-2. UPS Cabinet Clearances

From Top of Cabinet
300 mm (12") working space
From Front of Cabinet
900 mm (36") working space
From Back of Cabinet
See Table No: 3-3
From Right Side of Cabinet
See Table No: 3-3
From Left Side of Cabinet
See Table No: 3-3
The basic environmental requirements for operation of the UPS are:
• Ambient Temperature Range: 0–40°C (32–104°F)
• Recommended Operating Range: 20–25°C (68–77°F)
• Maximum Relative Humidity: 95%, noncondensing

Table 3-3. 93E Required Clearance

93E Required Clearance for paralleled adjacent UPS or UPS and adjacent PDU
15kVA/20kVA/30kVA/40kVA
ambient
L1(mm)
25
C
o
≥120
30
C
o
35
o
C
≥150
40
C
o
Notes:
• L1- clearance to the rear wall.
• L2- clearance between the adjacent paralleled UPS or UPS and adjacent PDU. Parallel UPS should be as
close as possible.
• Some models that feature rear connections also require additional rear clearance to enable installation and
connection.
60kVA/80kVA
L2(mm)
L1(mm)
≥150
≤50
≥200
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
UPS Installation Plan and Unpacking
L2(mm)
≤50
3-3