Deutschmann Automation GmbH & Co. KG
14 Installation guidelines
14.1 Installation of the module
The module with the dimensions 46 x 117 x 111 mm (W x D x H) has been developed for switch
cabinet use (IP 20) and can thus be mounted only on a standard mounting channel (deep DIN-
rail to EN 50022).
14.1.1 Mounting
•
Engage the module from the top in the top-hat rail and swivel it down so that the module
engages in position.
•
Other modules may be rowed up to the left and right of the module.
•
There must be at least 5 cm clearance for heat dissipation above and below the module.
•
The standard mounting channel must be connected to the equipotential bonding strip of the
switch cabinet. The connection wire must feature a cross-section of at least 10 mm².
14.1.2 Removal
•
First disconnect the power supply and signal lines.
•
Then push the module up and swivel it out of the top-hat rail.
Vertical installation
The standard mounting channel may also be mounted vertically so that the module is mounted
turned through 90°.
14.2
Wiring
14.2.1 Connection systems - PROFINET
The following connection systems must resp. may be used when wiring the module:
•
Standard screw-type/plug connection (power supply + Debug)
•
8-pin RJ45-plug-in connection (PROFINET-IO-connection)
a) In the case of standard screw-type terminals, one lead can be clamped per connection point. It
is best to then use a screwdriver with a blade width of 3.5 mm to firmly tighten the screw.
Permitted cross-sections of the line:
•
Flexible line with wire-end ferrule:
•
Solid conductor:
•
Tightening torque:
b) The plug-in connection terminal strip is a combination of standard screw-type terminal and
plug connector. The plug connection section is coded and can thus not be plugged on the
wrong way round.
14.2.2 Connection systems - CANopen
The following connection systems must resp. may be used when wiring the module:
•
Standard screw-type/plug connection (power supply + Debug)
•
9-pin D-SUB plug connector (CANopen
29.9.20
Fieldbus-Gateway UNIGATE
1 x 0.25 ... 1.5 mm²
1 x 0.25 ... 1.5 mm²
0.5 ... 0.8 Nm
®
)
®
CX C4Map - PROFINET V. 1.0
Installation guidelines
39