Menu Code 10 - How To Set A Slow Flow Amount - Bennett 3000 Series Operator's Manual

Retail dispensers with 210 electronics
Hide thumbs Also See for 3000 Series:
Table of Contents

Advertisement

Menu Code 10 - How to Set a Slow Flow Amount

NOTE: This menu code is only used when the dispenser is equipped with valves.
This code applies to console prepay sales or optional local preset sales only. In both cases,
the flow of fuel is stopped at a pre-selected amount. At fast flow rates the solenoid valve
may not be able to react fast enough to stop at the exact pre-selected amount. A two stage
solenoid valve is used so that the fast flow stage of the valve is closed when a selected unit
of volume remains to be dispensed and allows the slow flow stage of the valve to complete
the sale. Dispensers with higher flow rates require a longer period of time to react and shut-
down the valve. For example, at a setting of 0.200 (default), the solenoid valve will go into
slow flow stage when there is 2/10 (two tenths) of a unit remaining to be delivered to reach
the pre-selected amount. The minimum volume that can be selected is 0.1 units and the
maximum volume that can be selected is 9.9.
.1
.2
.3
8 - 18 (GPM)
To select a slow flow amount, follow this procedure:
1. After the Manager's Mode has been accessed, press the number 1 and 0, then the
MODE button on the keypad. See Figure 1.
If the dispenser has not been programmed since it came from the factory, the number
0.200 appears in the main display. See Figure 2. This is the default setting. The PPV
display shows the dispenser is in Menu Code 10.
2. To change the setting, use the 0 through 9 buttons on the keypad to enter a new volume
amount. The software allows a from .1 to .9 units. See suggested settings above.
NOTE: If an error is made, press the correct number. The new number replaces the
error.
3. When the correct setting appears in the volume display, press the ENTER button to
save the selection.
4. Press the CANCEL button to exit this menu code.
Example - If you have a dispenser that dispenses 18 g.p.m. what value should you set in
mode 10?
Answer - Anything from .5 units or higher.
3000 Series Retail Operators Manual 108796 Rev C, 07/05
.4
.5
.6
.7
30 - 68 (LPM)
Suggested Settings
24
.8
.9 (VOLUME UNITS)
18 & Higher (GPM)
68 & Higher (LPM)
Fig. 1
Fig. 2