Data Communication Wiring for Use with a Console Finishing the Dispenser Wiring Installation Dispenser Start-Up and Checklist Final Installation Check List Field Wiring and Grounding Diagrams Remote Self-Contained How to Calibrate the SB-100 Meter Site Audit Form Bennett Warranty 105894 Rev G 12-6-16...
Environmental Standards® Health, Safety, Security & Environment (HSSE) policies. Note: Bennett Pump highly recommends all technicians observe HSSE policies defined by the supplier. Bennett Pump does not impose any restrictions or additional requirements contained in Environmental Standards® Health, Safety, Security & Envi- ronment (HSSE) policies.
Product Specifications POWER REQUIREMENTS AC Power Input, Electronic 115 VAC, 60 Hz. at 560W or 230 VAC, 50 Hz. at 560W. DC Power Supply Output +5VDC 5.0 Amps Max, +12 VDC 1.75 Amps Max. DC Power Supply Output +24 VDC 2.75 Amps Max. Lead-Acid Battery Output 12 VDC, 2.0 Ampere Hours Nickel-Cadmium Battery Output...
Determining the Number of Supply Pipes Needed Determine the dispenser’s model number from the serial tag located on the side 1 lower rail of the dispenser. Locate the model number in the chart below to determine the number of product pipes required.
Determining the Correct Position of Product Supply Pipes The following chart indicates the relationship of the product inlets to the nozzle boots. Find the model number of the dispenser you are installing and determine the number of product inlets and their location. Exact inlet locations can be found on the base diagrams later in this manual.
Examine the shipment immediately upon arrival to make certain there has been no damage or loss in transit. Bennett Pump Company, as shipper, is not liable for the hazards of transportation. Please make damage claims directly to the truck line.
The dispenser must be mounted on a concrete foundation. Do not pour concrete around the product pipes or electrical conduit. The use of a UL approved containment sump designed for the Bennett Dispenser Model used is highly recommended. Follow the containment sump manufacture’s installation instructions for proper installation.
The dispenser must be bolted to the island. Do not skip this step. Check with Federal, State and Local Codes for conduit use in your area. Bennett Pump Company recommends the use of Rigid metal conduit.
Wiring Instructions DETERMINING THE NUMBER OF WIRES NEEDED (115 or 230 Volt installations). Determine the wires needed in each step and add the number of wires from each step together to determine total number of wires required. Total of 4 steps. Step 1.
Page 18
Wiring Notes: These notes are must do requirements to ensure a successful installation that meets Bennett’s limited warranty requirements. 1. Check with Federal, State and Local Codes for conduit use in your area. Bennett recommends rigid metal conduit. 2. Use only stranded wire with listed gas and oil resistant insulation. Do not use wire smaller than listed on the Bennett wiring diagrams.
WARNING: Failure to properly ground the equipment can cause injury or damage to the equipment and will void the Bennett limited warranty. This product must be properly grounded. Each dispenser requires a 12-gauge earth ground wire. Grounding provides a path of least resistance for electric current to reduce the risk of electric shock.
Connecting Pump Motor Power for Remote Dispensers The remote dispensers require a submerged pump control relay box, such as Red Jacket or F.E. Petro across the line starters. Check with those manufactures for information on control relay boxes. Termination of Field Wiring for Pump Motor Power of Remote Dispensers Follow the chart below by locating the model number of the dispenser you are installing in the chart.
Installation of the RC Networks An RC Network is an electrical noise suppression device. It is used on AC power devices such as coils and across relay contacts. Coils are used to operate AC devices, such as solenoid dispensing valves and AC power relays or contactors.
Installation of the RC Networks 4th Product: Connect the Violet 14ga. L1 - 120 or 240 VAC (HOT) wire from the 4th motor power circuit breaker to the power board as indicated in the chart below. Connect the White 120VAC Neutral or the Black L2-240VAC wire from the 4th motor power circuit breaker to the power board as indicated in the chart below.
Data Communication Wiring for Use with a Console or Controller Data wires are required for operation of each fueling position with a control console or controller. The data wires can be put in the same conduit as the other pump wiring. Each side (fueling position) of a dispenser requires one Orange and one Yellow 18-gauge, or larger, data wires.
WARNING: To prevent injury, make sure impact valves and submerged pump breakers are off. IMPORTANT NOTE The software in 2300 and 2400 Series Bennett blender dispensers controls Product “A” and “D” pump motors. When the blend product is activated, no Product “B” field motor wire is required.
Page 25
Dispenser Start Up & Checklist 4. Put the Product D (2448 or 2444 one sided units only) pump handle in the ON position. Use a voltmeter to verify 115 or 230 Volts AC on Terminal 19 of the terminal block. Use Terminal 2 as Neutral.
Final Installation Checklist Item Procedure Completed √ Shear valve installed per valve manufacturer recommendations. Self-contained pumps must have a vacuum actuated pressure regulating valve when used with above ground tanks. Self-contained pumps require a check valve. All hanging hardware must be checked for continuity. The units must be properly bolted to the island.
How to Operate Dispenser Figure 14A - 2300/2400 Series Remote 105894 Rev G 12-6-16...
Page 28
115VAC or 230VAC for its operation and may not be changed in the field. ( attempting to do this will void the Bennett limited warranty) Electronic power for all dispensers at the installation must be wired to the same AC line phase or damage will result to the dispensers. This will avoid a cross phase condition on the remote relay control wires.
Page 29
How to Operate Dispenser Figure 15A - 2300/2400 Series Self-Contained 105894 Rev G 12-6-16...
How to Calibrate the SB-100 Meter The Bennett SB-100 Meter is built to maintain accurate measurement under normal operating conditions. The meter is a positive displacement device with rods and pistons, which require a break in period. The meter is calibrated at the factory using a solvent for safety purposes, and must be calibrated after it has been installed.
Was the Bennett Warranty statement reviewed with the station Manager / Owner? Name of Owner / Manager? _________________________________________ Were all Bennett installation instructions in the Installation Manual followed? (If not, please list on the next page. 105894 Rev G 12-6-16...
Page 32
Horizon 2 Audit Form 108422 Exceptions to Bennett Installation Instructions—(Please list anything out of the ordinary or worth mentioning that might affect safety dispensing equipment operation). ___________________________________________________________________________________ ___________________________________________________________________________________ ___________________________________________________________________________________ ___________________________________________________________________________________ ___________________________________________________________________________________ ___________________________________________________________________________________ ___________________________________________________________________________________ ___________________________________________________________________________________ ___________________________________________________________________________________ ___________________________________________________________________________________ ___________________________________________________________________________________ ___________________________________________________________________________________ ___________________________________________________________________________________ ___________________________________________________________________________________...
PCI SSC - Legal Terms and Conditions PCI SSC’s approval only applies to PEDs that are identical to the PED tested by a PCI Security Standards Council recognized laboratory. If any aspect of the PED is different from that which was test- ed by the laboratory - even if the PED conforms to the basic product description contained the letter, then the PED model should not be considered approved, nor promoted as approved.