5.5.7.12 UV Prot. time
This function is used to set inverter connection time after input voltage drops below
Under Voltage limit, set at 90V.
For example: if UV Prot. time is set at 60 seconds, and Vin voltage drops below 90V
at 9.00, the inverter stays connected to the grid (at 0 power) up to 9.01.
Power-One sets this time at 60 seconds. The user can change this setting and set it
from 1 second to 3600 seconds.
5.5.7.13 MPPT scan
This function is used to automatically detect input power max multiples.
5.5.7.14 Scan Interval
This function is used to set time interval for system max.multiple scan. Default setting
is 15 minutes.
MPPTscan En7Dis
Enable
Scan Interval
15 min