C-## Frequency Control Functions - GE AF-650 GP Programming Manual

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Parameter Descriptions

3.5 C-## Frequency Control Functions

Parameter group related to the Jump Frequencies, Multi-
step Frequencies, Job set-up, and Frequency Settings 2 and
3.
3.5.1 C-0# Frequency Control Functions
Parameters to configure Jump Frequencies 1, 2, 3, and 4,
and Multi-step Frequencies 1 through 8.
C-01 Jump Frequency From [Hz]
Array [4]
Range:
Function:
0 Hz
[0 - par. F-15
Some systems require that certain output
*
Hz]
frequencies or speeds are avoided due to
resonance problems in the system. Enter
the lower limits of the speeds to be
avoided.
C-02 Jump Speed From [RPM]
Array [4]
Range:
Function:
0 RPM
[0 - par. F-17
Some systems call for avoiding certain
*
RPM]
output speeds due to resonance
problems in the system. Enter the
lower limits of the speeds to be
avoided.
C-03 Jump Speed To [RPM]
Array [4]
Range:
Function:
0 RPM
[0 - par. F-17
Some systems call for avoiding certain
*
RPM]
output speeds due to resonance
problems in the system. Enter the
upper limits of the speeds to be
avoided.
C-04 Jump Frequency To [Hz]
Array [4]
Range:
Function:
0 Hz
[0 - par. F-15
Some systems call for avoiding certain
*
Hz]
output speeds due to resonance
problems in the system. Enter the upper
limits of the speeds to be avoided.
C-05 Multi-step Frequency 1 - 8
Array [8]
Range: 0-7
Range:
Function:
0 %
[-100 -
Enter up to 8 different preset references (0-7) in
*
100 %]
this parameter, using array programming. The
preset reference is stated as a percentage of the
value Ref
(parameter F-53 Maximum
MAX
DET-618D
AF-650 GP™ Programming Guide
C-05 Multi-step Frequency 1 - 8
Array [8]
Range: 0-7
Range:
Illustration 3.18 Preset Reference
Preset ref. bit
Preset ref. 0
Preset ref. 1
Preset ref. 2
Preset ref. 3
Preset ref. 4
Preset ref. 5
Preset ref. 6
Preset ref. 7
Table 3.12 Preset Reference Bits
3.5.2 C-2# Jog Set-Up
Parameters to configure Jog Speed, Jog Accel/Decel Time
and Quick Stop Decel Time.
C-20 Jog Speed [Hz]
Range:
5.0 Hz
*
02/2016 All rights reserved.
Function:
Reference). If a Ref
different from 0
MIN
(parameter F-52 Minimum Reference) is
programmed, the preset reference is calculated
as a percentage of the full reference range, that
is on the basis of the difference between Ref
and Ref
. Afterwards, the value is added to
MIN
Ref
. When using preset references, select
MIN
preset reference bit 0/1/2 [16], [17] or [18] for
the corresponding digital inputs in parameter
group E-##.
2
0
0
0
0
1
1
1
1
Function:
[0 - par.
The jog speed is a fixed output speed at
F-15 Hz]
which the frequency converter is running,
when the jog function is activated.
See also parameter C-22 Jog Accel/Decel
Time.
3
MAX
1
0
0
0
0
1
1
0
1
1
0
0
0
1
1
0
1
1
55
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents