Parameter Descriptions

3.15 RS-## Resolver Interface

RS-50 Poles
Range:
2
[2 - 8]
Set the pole number on the resolver.
*
3
3
The value is stated in the datasheet for resolvers.
RS-51 Input Voltage
Range:
7 V
[2 - 8 V] Set the input voltage to the resolver. The
*
RS-52 Input Frequency
Range:
10 kHz
[2 - 15 kHz] Set the input frequency to the resolver.
*
RS-53 Transformation Ratio
Range:
0.5
[0.1 - 1.1] Set the transformation ratio for the resolver.
*
RS-56 Encoder Sim. Resolution
Set the resolution and activate the encoder emulation function
(generation of encoder signals from the measured position from
a resolver). Use this function to transfer the speed or position
information from 1 frequency converter to another. To disable
the function, select [0] Disabled.
Option:
[0]
*
[1]
[2]
[3]
[4]
RS-59 Resolver Interface
Activate the OPCRES when the resolver parameters are selected.
To avoid damage to resolvers, adjust parameter RS-50 Poles and
parameter RS-53 Transformation Ratio before enabling this
parameter.
Option:
[0]
*
[1]
122
Function:
Function:
voltage is stated as RMS value.
The value is stated in the datasheet for resolvers.
Function:
The value is stated in the datasheet for
resolvers.
Function:
The transformation ration is:
V
Out
T
  =  
ratio
V
In
The value is stated in the datasheet for
resolvers.
Function:
Disabled
512
1024
2048
4096
Function:
Disabled
Enabled
3.16 Parameter Data Check
3.16.1 Last 10 Changes
Displays a list of the 10 last changes made to the
parameters in the present parameter setup. This allows for
any corrections of the last 10 changes.
3.16.2 Since Factory Settings
Displays a list of all the parameter changes since the
factory settings of the drive or since the last factory restore
of parameters.
02/2016 All rights reserved.