Parameter Descriptions
3.4.2 E-1# Additional Accel/Decel Ramps
Parameters to configure the Accel/Decel Ramps 2, 3, and 4.
E-10 Accel Time 2
Range:
3
3
3.00
[0.01 -
s
3600 s]
*
E-11 Decel Time 2
Range:
3.00
[0.01 -
s
3600 s]
*
E-12 Accel Time 3
Range:
3.00
[0.01 -
s
3600 s]
*
E-13 Decel Time 3
Range:
3.00
[0.01 -
s
3600 s]
*
48
Function:
Enter the accel time from 0 RPM to the nominal
motor speed n
. Select a accel time such that
s
the output current does not exceed the current
limit in parameter F-43 Current Limit during
ramping. The value 0.00 corresponds to 0.01 s
in speed mode. See decel time in
parameter E-11 Decel Time 2.
t
  s  x n
  RPM
acc
s
Par .  E − 10  =  
 ref   RPM
Function:
Enter the decel time from the nominal motor
speed n
to 0 RPM. Select a decel time such that
s
no overvoltage occurs in the frequency
converter due to regenerative operation of the
motor, and such that the generated current does
not exceed the current limit set in
parameter F-43 Current Limit. The value 0.00
corresponds to 0.01 s in speed mode. See accel
time in parameter E-10 Accel Time 2.
t
  s  x n
  RPM
dec
s
Par .  E − 11  =  
 ref   RPM
Function:
Enter the accel time from 0 RPM to the
nominal motor speed n
. Select a accel time
s
such that the output current does not exceed
the current limit in parameter F-43 Current Limit
during ramping. The value 0.00 corresponds to
0.01 s in speed mode. See decel time in
parameter E-13 Decel Time 3.
Function:
Enter the decel time from the nominal motor
speed n
to 0 RPM. Select a decel time such that
s
no overvoltage occurs in the inverter due to
regenerative operation of the motor, and such
that the generated current does not exceed the
current limit set in parameter F-43 Current Limit.
The value 0.00 corresponds to 0.01 s in speed
mode. See accel time in parameter E-12 Accel
Time 3.
t
  s  x n
  RPM
dec
s
Par .  E − 13  =  
 ref   RPM
E-14 Accel Time 4
Range:
3.00
[0.01 -
s
3600 s]
*
E-15 Decel Time 4
Range:
3.00
[0.01 -
s
3600 s]
*
3.4.3 E-2# Digital Output
Parameters to configure terminal 27 and 29 digital outputs
controlled by serial communications and to configure Relay
1 and Relay 2.
Parameters for configuring the output functions for the
output terminals. The 2 solid-state digital outputs are
common for terminals 27 and 29. Set the I/O function for
terminal 27 in parameter E-51 Terminal 27 Mode, and set
the I/O function for terminal 29 in parameter E-52 Terminal
29 Mode. These parameters cannot be adjusted while the
motor is running.
[0]
No operation
[1]
Control ready
[2]
Drive ready
[3]
Drive ready /
remote
control
[4]
Enable / no
warning
[5]
Drive running
[6]
Running / no
warning
02/2016 All rights reserved.
Function:
Enter the accel time from 0 RPM to the rated
motor speed n
. Select a accel time such that
s
the output current does not exceed the current
limit in parameter F-43 Current Limit during
ramping. The value 0.00 corresponds to 0.01 s
in speed mode. See decel time in
parameter E-15 Decel Time 4.
t
  s  x n
  RPM
acc
s
Par .  E − 14  =  
 ref   RPM
Function:
Enter the decel time from the nominal motor
speed n
to 0 RPM. Select a decel time such that
s
no overvoltage occurs in the inverter due to
regenerative operation of the motor, and such
that the generated current does not exceed the
current limit set in parameter F-43 Current Limit.
The value 0.00 corresponds to 0.01 s in speed
mode. See accel time in parameter E-14 Accel
Time 4.
t
  s  x n
  RPM
dec
s
Par .  E − 15  =  
 ref   RPM
Default for all digital outputs and relay
outputs
The control board receives supply voltage.
The frequency converter is ready for
operation and applies a supply signal on
the control board.
The frequency converter is ready for
operation and is in Auto mode.
Ready for operation. No start or stop
command is been given (start/disable).
There are no warnings.
Motor is running.
Output speed is higher than the speed set
in parameter H-81 Min Speed for Function at
DET-618D