How to Program

2.1.7 Initial Commissioning

The easiest way of carrying out the initial commissioning is by pressing [Quick Menu] and following the quick set-up
2
2
procedure (read Table 2.3 from left to right). The example applies to open-loop applications.
Press
Parameter K-01 Language
Parameter K-02 Motor Speed Unit
Parameter P-02 Motor Power [HP] or
Parameter P-07 Motor Power [kW]
Parameter F-05 Motor Rated Voltage
Parameter F-04 Base Frequency
Parameter P-03 Motor Current
Parameter P-06 Base Speed
Parameter F-01 Frequency Setting 1
Parameter F-02 Operation Method
Parameter F-07 Accel Time 1
Parameter F-08 Decel Time 1
Parameter F-10 Electronic Overload
Parameter F-15 Motor Speed High Limit
[Hz] or Parameter F-17 Motor Speed High
Limit [RPM]
Parameter F-16 Motor Speed Low Limit
[Hz] or Parameter F-18 Motor Speed Low
Limit [RPM]
Parameter H-08 Reverse Lock
18
Quick Start
Set language
Set motor speed in Hz or RPM
Set Motor nameplate power
Set Nameplate voltage
Set Nameplate frequency
Set Nameplate current
Set Nameplate speed in RPM
Set reference source
Select which reference site to activate
Set the accel time with reference to synchronous motor
speed, n
s
Set the decel time time with reference to synchronous
motor speed, n
s
Set motor thermal protection
Set motor speed high limit in Hz or RPM
Set motor speed low limit in Hz or RPM
Set allowed rotation direction