Parameter Descriptions
EN-14 Link Duplex
Option:
Function:
Forces the duplex for each port to full or half
duplex. If parameter EN-12 Auto Negotiation is
set to: [ON], this parameter is read-only.
[0]
Half Duplex
[1]
Full Duplex
*
EN-20 Control Instance
Range:
Function:
[None, 20, 21, 23,
Read-only. Displays the connection to the
100, 101, 103]
master. In Ethernet/IP: If no CIP
connection is present, None is displayed.
EN-21 Process Data Config Write
Range:
Function:
[[0 - 9] PCD read 0 - 9] Configuration of readable process
data.
EN-22 Process Data Config Read
Range:
Function:
[[0 - 9] PCD read 0 - 9] Configuration of readable process
data.
EN-23 Process Data Config Write Size
Range:
Function:
16
[8 - 32] Sets the number of bits being sent from the
*
frequency converter as process data. The setting
counts from right (LSB). The value 1 means that
only the least significant bit of the signal is
transferred from the frequency converter.
EN-24 Process Data Config Read Size
Range:
Function:
16
[8 - 32] Sets the number of bits being sent to the
*
frequency converter as process data. The setting
counts from right (LSB). The value 1 means that
only the least significant bit of the signal is
transferred to the frequency converter. The
preceding bits are set to zero.
EN-27 Primary Master
Range:
Function:
0
[0 -
Controls the Master's access to the process
*
4294967295]
data. The value zero (0.0.0.0) means that
other masters can take control of the drive
immediately if the connection is lost or
closed. Setting an IP number means that
only a master with this value can establish a
connection for controlling the drive. In
systems with backup masters, this parameter
should be left to the value zero (0.0.0.0).
DET-618D
AF-650 GP™ Programming Guide
EN-28 Store Data Values
Option:
[0]
Off
*
[1]
Store All
set-ups
EN-29 Store Always
Option:
[0]
Off
*
[1]
On
EN-30 Warning parameter
Range:
[0000–
FFFF hex]
EN-31 Net Reference
Option:
[0]
Off Reference from the network is not active.
*
[1]
On Reference from the network is active.
02/2016 All rights reserved.
Function:
This parameter activates a function that stores
all parameter values in the non-volatile memory
(EEPROM) thus retaining parameter values at
power-down.
The parameter returns to [0] Off.
The store function is inactive.
All parameter values are stored in the non-
volatile memory, in all 5 set-ups.
Function:
Activates function that always stores received
parameter data in non-volatile memory (EEPROM).
Function:
Read-only. Displays the Ethernet/IP specific 16-bit
status-word.
Bit
Description
0
Owned
1
Not used
2
Configured
3
Not used
4
Not used
5
Not used
6
Not used
7
Not used
8
Minor recoverable fault
9
Minor unrecoverable fault
10
Major recoverable fault
11
Major unrecoverable fault
12
Not used
13
Not used
14
Not used
15
Not used
Table 3.23 Bit Description
Function:
Read-only. Displays the reference source in Instance
21/71.
3
3
117