GE AF-650 GP Programming Manual page 126

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Parameter Descriptions
ID-21 Historic Log: Value
Array [50]
Range:
Function:
0
[0 -
View the value of the logged event.
*
2147483647]
Interpret the event values according to
Table 3.24:
Digital input
Digital output Decimal value. See
Warning word Decimal value. See
Alarm word
Status word
Control word
Extended
status word
Table 3.24 Logged Events
ID-22 Historic Log: Time
Array [50]
Range:
Function:
0 ms
[0 - 2147483647
View the time at which the logged
*
ms]
event occurred. Time is measured in
ms since frequency converter start. The
maximum value corresponds to
approximately 24 days, which means
that the count restarts at 0 after this
time period.
DET-618D
AF-650 GP™ Programming Guide
Decimal value. See
parameter DR-60 Digital
Input for description after
converting to binary
value.
parameter DR-66 Digital
Output [bin] for a
description after
converting to binary
value.
parameter DR-92 Warning
Word for a description.
Decimal value. See
parameter DR-90 Alarm
Word for a description.
Decimal value. See
parameter DR-03 Status
Word for a description
after converting to binary
value.
Decimal value. See
parameter DR-00 Control
Word for a description.
Decimal value. See
parameter DR-94 Ext.
Status Word for a
description.
02/2016 All rights reserved.
3.17.4 ID-3# Alarm Log
View up to 10 alarm logs. The data is stored in array
parameters, where [0] is the most recent and [9] is the
oldest data. Error codes, values, and time stamp can be
viewed for all logged data.
ID-30 Fault Log: Error Code
Range:
Function:
0
[0 - 255] View the fault code and look up its meaning in
*
chapter 5 Troubleshooting.
ID-31 Alarm Log: Value
Array [10]
Range:
Function:
0
[-32767 - 32767] View an extra description of the error. This
*
parameter is mostly used in combination
with alarm 38, internal fault.
ID-32 Alarm Log: Time
Array [10]
Range:
Function:
0 s
[0 - 2147483647 s] View the time when the logged event
*
occurred. Time is measured in s from
frequency converter start-up.
3.17.5 ID-4# Drive Identification
Parameters to view the information about the hardware
and software configuration of the drive.
ID-40 Drive Type
Range:
Function:
0
[0 - 6]
View the frequency converter type.
*
ID-41 Power Section
Range:
Function:
0
[0 - 20]
View the power section.
*
ID-42 Voltage
Range:
Function:
0
[0 - 20]
View the voltage.
*
ID-43 Software Version
Range:
Function:
0
[0 - 5]
View the SW version
*
ID-44 GE Model Number
Range:
Function:
0
[0 - 40] View the model number string used for reordering
*
the frequency converter in its original configu-
ration.
3
3
125

Advertisement

Table of Contents
loading

Table of Contents