5.1.1 Reference Handling
Select the drive configuration mode in par. H-40 Configuration Mode.
[0] Open Loop
[3] Closed Loop
Open Loop
For open loop operation, the reference represents the desired output speed of the drive.
The speed reference value:
Closed Loop
For closed loop operation, the reference represents the setpoint.
NB!
In closed loop operation, par. F-52 Minimum Reference and par. F-16 Motor Speed Low Limit [Hz] must be set to 0 Hz. Set the par. F-15 Motor Speed High Limit
[Hz] to a value greater than the setting in par. F-53 Maximum Reference.