Parameter Descriptions

3.10 O-## Options/Comms

Parameter group related to communications and options.
3.10.1 O-0# General Settings
3
3
Parameters to configure the general settings for communi-
cations and options.
O-01 Control Site
Option:
[0]
Digital and
*
ctrl.word
[1]
Digital only
[2]
Controlword
only
O-02 Control Word Source
Option:
[0]
None
[1]
Drive RS485
*
[2]
Drive USB
[3]
Option A
[4]
Option B
[30] External Can
96
Function:
The setting in this parameter overrides
the settings in parameter O-50 Coasting
Select to parameter O-56 Preset Reference
Select.
Control by using both digital input and
control word.
Control by using digital inputs only.
Control by using control word only.
Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
Select the source of the control word: 1 of 2
serial interfaces or 4 installed options. During
initial power-up, the frequency converter
automatically sets this parameter to [3] Option
A if it detects a valid fieldbus option module
installed in slot A. When the option is
removed, the frequency converter detects a
configuration change, sets
parameter O-02 Control Word Source to default
setting [1] FC RS485, and trips. If an option is
installed after initial power-up, the setting of
parameter O-02 Control Word Source does not
change, but the frequency converter trips and
shows: Alarm 67, Option Changed.
When retrofitting a bus option into a
frequency converter that did not have a bus
option installed earlier, change the control to
bus-based. This change is required for safety
reasons to avoid an unintended change.
02/2016 All rights reserved.
O-03 Control Word Timeout Time
Range:
Function:
1 s
[0.1 -
Enter the maximum time expected to pass
*
18000 s]
between the reception of 2 consecutive
messages. If this time is exceeded, it indicates
that the telegram communication has stopped.
The function selected in parameter O-04 Control
Word Timeout Function is then carried out. A
valid control word triggers the timeout counter.
O-04 Control Word Timeout Function
Select the timeout function. The timeout function activates when
the control word fails to be updated within the time period
specified in parameter O-03 Control Word Timeout Time.
Option:
Function:
NOTICE
To change the set-up after a timeout,
configure as follows:
1.
Set parameter K-10 Active Set-
up to [9] Multi set-up.
2.
Select the relevant link in
parameter K-12 This Set-up
Linked to.
[0]
Off
Resumes control via fieldbus (fieldbus or
*
standard), using the most recent control word.
[1]
Freeze
Freezes output frequency until communication
output
resumes.
[2]
Stop
Stops with auto restart when communication
resumes.
[3]
Jogging
Runs the motor at jog frequency until
communication resumes.
[4]
Max. speed Runs the motor at maximum frequency until
communication resumes.
[5]
Stop and
Stops the motor, then resets the frequency
trip
converter to restart:
Via the fieldbus.
Via [Reset].
Via a digital input.
[7]
Select
Changes the set-up after a control word
setup 1
timeout. If communication resumes after a
timeout, parameter O-05 End-of-Timeout
Function either resumes the set-up used
before the timeout, or retains the set-up
endorsed by the timeout function.
[8]
Select
See [7] Select set-up 1.
setup 2
[9]
Select
See [7] Select set-up 1.
setup 3
[10] Select
See [7] Select set-up 1.
setup 4