Io-## I/O Mode - GE AF-650 GP Programming Manual

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Parameter Descriptions

3.24 IO-## I/O Mode

3.24.1 IO-0# I/O Mode
OPCPRGIO has 3 analog inputs and 3 configurable analog
outputs. Use the parameters in this group to configure the
3
3
mode of the analog outputs.
Terminals can be programmed to provide voltage, current,
or digital output.
IO-03 Terminal X49/7 Mode
Select the output mode of analog terminal X49/7.
Option:
[0]
*
[1]
[2]
[3]
[4]
IO-04 Terminal X49/9 Mode
Select the output mode of analog terminal X49/9.
Option:
[0]
*
[1]
[2]
[3]
[4]
IO-05 Terminal X49/11 Mode
Select the output mode of analog terminal X49/11.
Option:
[0]
*
[1]
[2]
[3]
[4]
3.24.2 IO-1# Analog Input X49/1
IO-10 Terminal X49/1 Low Voltage
Range:
0.07 V
[0 - par.
*
IO-12 V]
IO-11 Terminal X49/1 Low Current
Range:
4 mA
[0 - par.
*
IO-13 mA]
160
Function:
Voltage 0-10V
Voltage 2-10V
Current 0-20mA
Current 4-20mA
Digital
Function:
Voltage 0-10V
Voltage 2-10V
Current 0-20mA
Current 4-20mA
Digital
Function:
Voltage 0-10V
Voltage 2-10V
Current 0-20mA
Current 4-20mA
Digital
Function:
Enter the voltage (V) that corresponds to
the low reference value (set in
parameter IO-14 Term. X49/1 Low Ref./
Feedb. Value).
Function:
Enter the voltage (mA) that corresponds
to the low reference value (set in
parameter IO-14 Term. X49/1 Low Ref./
Feedb. Value).
IO-12 Terminal X49/1 High Voltage
Range:
10 V
[par. IO-10 -
*
10 V]
IO-13 Terminal X49/1 High Current
Range:
20 mA
[par. IO-11 -
*
20 mA]
IO-14 Term. X49/1 Low Ref./Feedb. Value
Range:
0
[-999999.999 -
*
999999.999]
IO-15 Term. X49/1 High Ref./Feedb. Value
Range:
100
[-999999.999 -
*
999999.999]
IO-16 Term. X49/1 Filter Time Constant
Range:
0.001 s
[0.001 - 10
*
s]
IO-17 Term. X49/1 Live Zero
This parameter gives the possibility of disabling live zero
monitoring. E.g. for use as decentral I/O.
Option:
[0]
[1]
*
02/2016 All rights reserved.
Function:
Enter the voltage (V) that corresponds to
the low reference value (set in
parameter IO-15 Term. X49/1 High Ref./
Feedb. Value).
Function:
Enter the voltage (V) that corresponds to
the low reference value (set in
parameter IO-15 Term. X49/1 High Ref./
Feedb. Value).
Function:
Enter the reference or feedback value (in
RPM, Hz, bar, etc.) that corresponds to the
voltage or current set in
parameter IO-10 Terminal X49/1 Low
Voltage/parameter IO-11 Terminal X49/1
Low Current.
Function:
Enter the reference or feedback value (in
RPM, Hz, bar, etc.) that corresponds to
the voltage or current set in
parameter IO-12 Terminal X49/1 High
Voltage/parameter IO-13 Terminal X49/1
High Current.
Function:
Enter the filter time constant. This is a
first-order digital low pass filter time
constant for suppressing electrical noise
in terminal X49/1. A high time constant
value improves dampening but also
increases the delay through the filter.
Function:
Disabled
Enabled
DET-618D