Parameter Descriptions
Digital input function
Counter B (up)
Counter B (down)
Reset Counter B
Mech. Brake Feedb.
Mech. Brake Feedb. Inv.
Table 3.6 Functions for Digital Inputs
General Purpose Drives standard terminals are 18, 19, 27, 29, 32, and 33. OPCGPIO Option Module terminals are X30/2,
X30/3, and X30/4.
Functions dedicated to only one digital input are stated in the associated parameter.
All digital inputs can be programmed to these functions:
[0]
No
No reaction to signals transmitted to the
operation
terminal.
[1]
Reset
Resets frequency converter after a TRIP/ALARM.
Not all alarms can be reset.
[2]
Coast
Coasting stop, inverted input (NC). The
inverse
frequency converter leaves the motor in free
mode. Logic '0' => coasting stop.
[3]
Coast and
Reset and coasting stop Inverted input (NC).
reset
Leaves motor in free mode and resets
inverse
frequency converter. Logic '0' => coasting stop
and reset.
[4]
Quick stop
Inverted input (NC). Generates a stop in
inverse
accordance with quick-stop ramp time set in
parameter C-23 Quick Stop Decel Time. When
motor stops, the shaft is in free mode. Logic '0'
=> Quick-stop.
[5]
DC-brake
Inverted input for DC braking (NC). Stops
inverse
motor by energizing it with a DC current for a
certain time period. See parameter B-01 DC
Brake Current to parameter B-03 DC Brake Cut In
Speed [RPM]. The function is only active when
the value in parameter B-02 DC Braking Time is
different from 0. Logic '0' => DC braking.
[6]
Stop
Stop Inverted function. Generates a stop
inverse
function when the selected terminal goes from
logical level '1' to '0' . The stop is performed
according to the selected ramp time
(parameter F-08 Decel Time 1,
parameter E-11 Decel Time 2,
parameter E-13 Decel Time 3,
parameter E-15 Decel Time 4).
NOTICE
When the frequency converter is at the
torque limit and has received a stop
command, it may not stop by itself. To
ensure that the frequency converter
stops, configure a digital output to [27]
Torque limit & stopand connect this
digital output to a digital input that is
configured as coast.
DET-618D
AF-650 GP™ Programming Guide
Select
[63]
[64]
[65]
[70]
[71]
[8]
Start
[9]
Latched
start
[10] Reversing
[11] Start
reversing
[12] Enable
start
forward
[13] Enable
start
reverse
[14] Jog
[15] Preset
reference
on
[16] Preset ref
bit 0
[17] Preset ref
bit 1
[18] Preset ref
bit 2
02/2016 All rights reserved.
Terminal
29, 33
29, 33
All
All
All
(Default Digital input 18): Select start for a
start/stop command. Logic '1' = start, logic '0'
= stop.
The motor starts, if a pulse is applied for min.
2 ms. The motor stops when Stop inverse is
activated.
(Default Digital input 19). Change the direction
of motor shaft rotation. Select Logic '1' to
reverse. The reversing signal only changes the
direction of rotation. It does not activate the
start function. Select both directions in
parameter H-08 Reverse Lock. The function is
not active in process closed loop.
Used for start/stop and for reversing on the
same wire. Signals on start are not allowed at
the same time.
Disengages the counterclockwise movement
and allows for the clockwise direction.
Disengages the clockwise movement and
allows for the counterclockwise direction.
(Default Digital input 29): Use to activate jog
speed. See parameter C-20 Jog Speed [Hz].
Shifts between external reference and preset
reference. It is assumed that [1] External/preset
has been selected in parameter F-54 Reference
Function. Logic '0' = external reference active;
logic '1' = one of the eight preset references is
active.
Preset ref. bit 0,1, and 2 enables a choice
between one of the eight preset references
according to the table below.
Same as Preset ref bit 0 [16].
Same as Preset ref bit 0 [16].
3
3
45