Parameter Descriptions
F-43 Current Limit
Range:
Function:
160.0 %
[1.0 -
This is a true current limit function that
1000.0 %]
continues in the oversynchronous range.
*
However, due to field weakening the
motor torque at current limit will drop
accordingly when the voltage increase
stops above the synchronized speed of the
motor.
3.3.7 F-5# Extended References
Parameters to configure drive min/max reference and
reference function.
F-50 Reference Range
Option:
Function:
Select the range of the reference signal and the
feedback signal. Signal values can be positive only,
or positive and negative. The minimum limit may
have a negative value, unless [1] Speed closed loop
control or [3] Process is selected in
parameter H-40 Configuration Mode.
[0]
Min -
Select the range of the reference signal and the
Max
feedback signal. Signal values can be positive only,
or positive and negative. The minimum limit may
have a negative value, unless [1] Speed closed loop
control or [3] Process is selected in
parameter H-40 Configuration Mode.
[1]
-Max -
For both positive and negative values (both
+Max
directions, relative to parameter H-08 Reverse Lock).
*
F-51 Reference/Feedback Unit
Option:
Function:
Select the unit to be used in process PID control
references and feedbacks. Parameter H-40 Configu-
ration Mode must be either [3] Process or [8]
Extended PID Control.
[0]
None
*
[1]
%
[2]
RPM
[3]
Hz
[4]
Nm
[5]
PPM
[10]
1/min
[12]
Pulse/s
[20]
l/s
[21]
l/min
[22]
l/h
[23]
m3/s
[24]
m3/min
[25]
m3/h
[30]
kg/s
[31]
kg/min
DET-618D
AF-650 GP™ Programming Guide
F-51 Reference/Feedback Unit
Option:
[32]
kg/h
[33]
t/min
[34]
t/h
[40]
m/s
[41]
m/min
[45]
m
[60]
°C
[70]
mbar
[71]
bar
[72]
Pa
[73]
kPa
[74]
m WG
[80]
kW
[120] GPM
[121] gal/s
[122] gal/min
[123] gal/h
[124] CFM
[125] ft3/s
[126] ft3/min
[127] ft3/h
[130] lb/s
[131] lb/min
[132] lb/h
[140] ft/s
[141] ft/min
[145] ft
[150] lb ft
[160] °F
[170] psi
[171] lb/in2
[172] in WG
[173] ft WG
[180] HP
F-52 Minimum Reference
Enter the minimum reference. The minimum reference is the
lowest value obtainable by summing all references.
Minimum reference is active only when parameter F-50 Reference
Range is set to [0] Min.- Max.
The minimum reference unit matches:
Range:
0 ReferenceFeed-
backUnit
02/2016 All rights reserved.
Function:
The configuration of parameter H-40 Configuration Mode:
for [1] Speed closed loop, RPM; for [2] Torque, Nm.
The unit selected in parameter F-51 Reference/Feedback
Unit.
[-999999.999 - par.
F-53 ReferenceFeed-
*
backUnit]
3
3
Function:
41