Parameter Descriptions
H-30 Motor Speed Monitor Function
Option:
3
3
[0]
Disabled
*
[1]
Warning
[2]
Trip
[3]
Jog
[4]
Freeze
Output
[5]
Max Speed
[6]
Switch to
Open Loop
[7]
Select
Setup 1
[8]
Select
Setup 2
[9]
Select
Setup 3
[10] Select
Setup 4
[11] Stop & Trip
[12] Trip/
Warning
[13] Trip/Catch
68
Function:
Solid line
Parameter DR-48 Speed Ref. After
Ramp [RPM]
Dotted
Parameter H-31 Motor Speed
line
Monitor Max
Illustration 3.24 Speed Reference and
Maximum Allowed Speed Difference
The frequency converter reports warning 101,
Speed monitor when the speed is outside the
limit.
The frequency converter trips and reports
alarm 101, Speed monitor.
The frequency converter reports alarm 101,
Speed monitor in running mode and warning
101, Speed monitor in stop or coast mode. This
option is only available in closed-loop
operation.
Select when there is a need to catch a load,
for example when mechanical braking fails.
This option is available in closed loop only.
The frequency converter trips and reports
alarm 101, Speed monitor in running mode. In
stop mode, the frequency converter catches
the flying load and reports warning 101, Speed
monitor.
In catch mode, the frequency converter
applies holding torque to control the zero
speed on a potentially malfunctioning brake
(closed loop). To exit this mode, send a new
02/2016 All rights reserved.
H-30 Motor Speed Monitor Function
Option:
Function:
start signal to the frequency converter. A
coast or Safe Torque Off also terminates the
function.
H-31 Motor Speed Monitor Max
Range:
100 RPM
[10 - 500 RPM]
*
H-32 Motor Speed Monitor Timeout
Range:
0.1 s
[0 - 60 s]
*
3.7.4 H-4# Advanced Settings
Parameters to configure advanced controls for Open/
Closed Loop, control principles: V/Hz, Adv. Vector,
Sensorless Vector, and Closed Loop Vector, Constant or
Variable Torque, and Overload Mode.
H-40 Configuration Mode
Option:
Function:
Select the application control principle to be
used when a remote reference (that is via
analog input or Network) is active. A remote
reference can only be active when
parameter F-02 Operation Method is set to [0]
Linked to Hand/Auto or [1] Remote.
[0]
Speed
Enables speed control (without feedback signal
open loop
from motor) with automatic slip compensation
*
for almost constant speed at varying loads. Set
the speed control parameters in parameter
group PI-0# Speed PID Control.
[1]
Speed
Enables speed closed-loop control with
closed
feedback. Obtain full holding torque at 0 RPM.
loop
For increased speed accuracy, provide a
feedback signal and set the speed PID control.
Set the speed control parameters in parameter
group PI-0# Speed PID Control.
[2]
Torque
Enables torque closed-loop control with
feedback. Only possible with Flux with motor
feedback option, parameter H-41 Motor Control
Principle.
NOTICE
This is valid for AF-650 GP only.
[3]
Process
Enables the use of process control in the
frequency converter. Set the process control
parameters in parameter groups PI-2# and
PI-3#.
[4]
Torque
Enables the use of torque open loop in Adv.
open loop
Vector Control mode (parameter H-41 Motor
Function:
Function:
DET-618D