GE AF-650 GP Programming Manual page 163

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Parameter Descriptions
IO-35 Term. X49/5 High Ref./Feedb. Value
Range:
100
[-999999.999 -
*
999999.999]
3
3
IO-36 Term. X49/5 Filter Time Constant
Range:
0.001 s
[0.001 - 10
*
s]
IO-37 Term. X49/5 Live Zero
Option:
[0]
Disabled This parameter gives the possibility of disabling
[1]
Enabled
*
3.24.5 IO-4# Output X49/7
OPCPRGIO has 3 analog inputs and 3 configurable analog
outputs. Use the parameters in this group to configure the
mode of the analog outputs.
Select the functionality of terminal X49/7.
IO-40 Terminal X49/7 Analogue Output
Option:
[0]
No operation
*
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor Current
[104]
Torque rel to limit
[105]
Torq relate to rated
[106]
Power
[107]
Speed
[108]
Torque
[109]
Max Out Freq
[139]
Bus ctrl. 0-20 mA
[141]
Bus ctrl 0-20mA t.o.
162
Function:
Enter the reference or feedback value (in
RPM, Hz, bar, etc.) that corresponds to
the voltage or current set in
parameter IO-32 Terminal X49/5 High
Voltage/parameter IO-33 Terminal X49/5
High Current.
Function:
Enter the filter time constant. This is a
first-order digital low pass filter time
constant for suppressing electrical noise
in terminal X49/5. A high time constant
value improves dampening but also
increases the delay through the filter.
Function:
live zero monitoring. E.g. for use as decentral I/O.
Function:
IO-42 Terminal X49/7 Min. Scale
Match the minimum output of terminal X49/7 with a required
value. The required value is defined as a percentage of the value
selected in parameter IO-40 Terminal X49/7 Analogue Output. To
know more about how this parameter works, see
parameter AN-52 Terminal 42 Output Max Scale.
The following example describes how the frequency converter
uses this parameter.
Example
Parameter IO-03 Terminal X49/7 Mode=[0] Voltage 0-10 V
Parameter IO-40 Terminal X49/7 Analogue Output=[100] Output
frequency
Parameter F-03 Max Output Frequency 1=200 Hz
Application requirement: If the output frequency is lower than 20
Hz, the output of terminal X49/7 should be 0 V. To fulfil the
example requirement, enter 10% in parameter IO-42 Terminal
X49/7 Min. Scale.
Range:
0 %
*
IO-43 Terminal X49/7 Max. Scale
Range:
100 %
*
IO-44 Terminal X49/7 Bus Control
This parameter contains the output level of terminal X49/7 if the
terminal is controlled by a fieldbus.
Range:
0 %
*
IO-45 Terminal X49/7 Timeout Preset
The frequency converter sends the value of this parameter to the
output terminal when the terminal is controlled by a fieldbus
and a timeout is detected.
Range:
0 %
*
3.24.6 IO-5# Output X49/9
OPCPRGIO has 3 analog inputs and 3 configurable analog
outputs. Use the parameters in this group to configure the
mode of the analog outputs.
IO-50 Terminal X49/9 Analogue Output
Select the functionality of terminal X49/9.
Option:
[0]
*
[100]
[101]
[102]
[103]
[104]
[105]
[106]
[107]
02/2016 All rights reserved.
Function:
[0 - 200 %]
Function:
[0 - 200 %]
Function:
[0 - 100 %]
Function:
[0 - 100 %]
No operation
Output frequency
Reference
Feedback
Motor Current
Torque rel to limit
Torq relate to rated
Power
Speed