GE AF-650 GP Programming Manual page 12

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Introduction
1.5.2 Pulse Start/Stop
Terminal 18 = parameter E-01 Terminal 18 Digital Input, [9]
Latched start.
Terminal 27 = parameter E-03 Terminal 27 Digital Input, [6]
Stop inverse.
Terminal 37 = Safe Torque Off (where available).
Illustration 1.7 Pulse Start/Stop
1.5.3 Speed Up/Down
Terminals 29/32 = Speed up/down
Terminal 18 = parameter E-01 Terminal 18 Digital
Input [9] Start (default).
Terminal 27 = parameter E-03 Terminal 27 Digital
Input [19] Freeze reference.
Terminal 29 = parameter E-04 Terminal 29 Digital
Input [21] Speed up.
Terminal 32 = parameter E-05 Terminal 32 Digital
Input [22] Speed down.
Illustration 1.8 Speed Up/Down
DET-618D
AF-650 GP™ Programming Guide
1.5.4 Potentiometer Reference
Voltage reference via a potentiometer
Illustration 1.9 Potentiometer Reference
02/2016 All rights reserved.
Reference Source 1 = [1] Analog input 53 (default).
Terminal 53, low voltage = 0 V.
Terminal 53, high voltage = 10 V.
Terminal 53, low reference/feedback = 0 RPM.
Terminal 53, high reference/feedback = 1500 RPM.
Switch S201 = OFF (U)
1
1
11

Advertisement

Table of Contents
loading

Table of Contents