1.5 Electrical Wiring

Illustration 1.2 Basic Wiring Schematic Drawing
A=Analog, D=Digital
Terminal 37 is used for Safe Torque Off. For Safe Torque Off installation instructions, refer to the Design and Installation
Guide DET-767.
*The brake chopper factory option must be ordered to use dynamic brake resistors
**This is available when ordering the brake chopper option on unit size 23 and above drives.
Very long control cables and analog signals may in rare cases, and depending on installation, result in 50/60 Hz ground
loops due to noise from mains supply cables.
If 50/60 Hz ground loops occur, consider breaking the shield or insert a 100 nF capacitor between shield and enclosure.
To avoid ground currents from both groups to affect other groups, connect the digital and analog inputs and outputs
separately to the common inputs (terminals 20, 55, and 39) of the frequency converter. For example, switching on the digital
input may disturb the analog input signal.
DET-618D