Parameter Descriptions
sioning if similar parameter settings are required in
different setups.
K-10 Active Set-up
Option:
3
3
[0]
Factory
setup
[1]
Set-up 1
*
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
[9]
Multi Set-
up
Use parameter K-51 Set-up Copy to copy a set-up to 1 or all
other set-ups. Stop the frequency converter before
switching between set-ups where parameters marked not
changeable during operation have different values. To avoid
conflicting settings of the same parameter within 2
different set-ups, link the set-ups together using
parameter K-12 This Set-up Linked to. Parameters which are
not changeable during operation are marked FALSE in the
parameter lists in chapter 4 Parameter Lists.
K-11 Edit Set-up
Option:
[0]
Factory
setup
[1]
Set-up 1
*
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
[9]
Active Set-
up
26
Function:
Select the set-up to control the frequency
converter functions.
Cannot be changed. It contains the GE data
set and can be used as a data source when
returning the other set-ups to a known state.
[1] Set-up 1 to [4] Set-up 4 are the 4 separate
parameter set-ups within which all parameters
can be programmed.
Remote set-up selections using digital inputs
and the serial communication port. This set-up
uses the settings from parameter K-12 This Set-
up Linked to. Stop the frequency converter
before making changes to open and closed
loop functions.
Function:
Select the set-up to be edited (that is
programmed) during operation; either the
active set-up or 1 of the inactive set-ups.
Cannot be edited but it is useful as a data
source to return the other set-ups to a known
state.
[1] Set-up 1 to [4] Set-up 4 can be edited freely
during operation, independently of the active
set-up.
Can also be edited during operation. Edit the
selected set-up from a range of sources:
Keypad, Drive RS485, Drive USB, or up to 5
Network sites.
Illustration 3.1 Edit Set-up
K-12 This Set-up Linked to
Option:
02/2016 All rights reserved.
Function:
To enable conflict-free changes from 1 set-up to
another during operation, link set-ups
containing parameters which are not
changeable during operation. The link ensures
synchronizing of the not changeable during
operation-parameter values when moving from
1 set-up to another during operation. Not
changeable during operation-parameters can be
identified by the label FALSE in the parameter
lists in chapter 4 Parameter Lists.
Parameter K-12 This Set-up Linked to is used by
[9] Multi set-up in parameter K-10 Active Set-up.
Multi set-up is used to move from 1 set-up to
another during operation (that is while the
motor runs).
Example:
Use multi set-up to shift from set-up 1 to Set-
up 2 while the motor runs. Program in set-up 1
first, then ensure that set-up 1 and set-up 2 are
DET-618D