Parameter Descriptions
DR-34 Heatsink Temp.
Range:
0 °C
[0 -
*
255 °C]
3
3
DR-35 Drive Thermal
Range:
0 %
[0 - 100 %]
*
DR-36 Drive Nominal Current
Range:
10.00 A
[0.01 -
*
10000 A]
DR-37 Drive Max. Current
Range:
16.00 A
[0.01 -
*
10000 A]
DR-38 Logic Controller State
Range:
0
[0 - 100] View the state of the event under execution by
*
DR-39 Control Card Temp.
Range:
0 °C
[0 - 100 °C] View the temperature on the control card,
*
DR-40 Trending Buffer Full
Option:
Function:
View whether the logging buffer is full (see
chapter 3.17.2 ID-1# Data Trending Settings). The
logging buffer is never full when
parameter ID-13 Trending Mode is set to [0] Log always.
[0]
No
*
[1]
Yes
DR-45 Motor Phase U Current
Range:
0 A
[0 - 10000 A] Shows the motor phase U
*
130
Function:
View the frequency converter heat sink
temperature. The cut-out limit is 90 ±5 °C
(194 ±9 °F), and the motor cuts back in at 60
±5 °C (140 ±9 °F).
Function:
View the percentage load on the inverter.
Function:
View the inverter nominal current, which
must match the nameplate data on the
connected motor. The data is used for
calculation of torque, motor overload
protection, and so on.
Function:
View the inverter maximum current,
which must match the nameplate data
on the connected motor. The data is
used for calculation of torque, motor
overload protection, and so on.
Function:
the LC controller.
Function:
stated in °C.
Function:
Facilitates monitoring of imbalance in the
motor currents, detection of weak motor
cables or imbalance in motor windings.
DR-46 Motor Phase V Current
Range:
0 A
[0 - 10000 A] Shows the motor phase V
*
DR-47 Motor Phase W Current
Range:
0 A
[0 - 10000 A] Shows the motor phase W
*
DR-48 Speed Ref. After Ramp [RPM]
Range:
0 RPM
*
DR-49 Current Fault Source
Range:
0
[0 - 8] Value indicates source of current faults including
*
3.18.4 DR-5# Ref. & Feedb.
Parameters to view the reference and feedback status
values.
DR-50 External Reference
Range:
0
[-200 - 200] View the total reference, the sum of digital,
*
DR-51 Pulse Reference
Range:
0
[-200 - 200] View the reference value from programmed
*
DR-52 Feedback[Unit]
Range:
0 Reference-
current.
RMS
FeedbackUnit
02/2016 All rights reserved.
Function:
Facilitates monitoring of imbalance in the
motor currents, detection of weak motor
cables or imbalance in motor windings.
Function:
Facilitates monitoring of imbalance in the
motor currents, detection of weak motor
cables or imbalance in motor windings.
Function:
[-30000 - 30000
This parameter specifies the
RPM]
reference given to the frequency
converter after the speed ramp.
Function:
short circuit, overcurrent, and imbalance of supply
voltage (from left):
1–4 Inverter
5–8 Rectifier
0 No fault recorded
Function:
analog, preset, fieldbus, and freeze references,
plus catch up and slow down.
Function:
digital inputs. The readout can also reflect the
impulses from an incremental encoder.
Function:
[-999999.999 -
View the feedback unit
999999.999
resulting from the selection
*
ReferenceFeed-
of unit and scaling in
backUnit]
parameter F-50 Reference
Range,
parameter F-51 Reference/
current.
RMS
current.
RMS
DET-618D