VSD Series Drives User Manual
Table 9-2: Quick Setup Parameters — M1 ➔ G1.1, continued
Code
Parameter
P1.1.12
Start Srce Hand
P1.1.13
StPt Source
Hand
P1.1.14
Start Srce Auto
P1.1.15
StPt Source Auto 0
9-4
Min.
Max.
1
3
0
3
1
4
4
For more information visit: www.johnsoncontrols.com
ID
Unit Default
Number Description
1
112
2
113
2
114
0
115
Eaton Technology
Powered by
November 2009
Parameter for Local
Start/Stop/Reverse control
location.
Default = Keypad
1 = Keypad
2 = DI-1 Start
3 = I/O Three Wire
Local speed setpoint selection:
0 = analog input AI-1
1 = analog input AI-2
2 = Speed Setpoint from Keypad
3 = Motor Potentiometer
Parameter for Remote Start/
Stop/Reverse control location.
Default = DI-1 Start
1 = Keypad
2 = DI-1 Start
3 = I/O Three Wire
4 = Fieldbus
Remote speed setpoint
selection:
0 = analog input AI-1
1 = analog input AI-2
2 = Speed Setpoint from Keypad
3 = Motor Potentiometer
4 = Speed Setpoint from
Fieldbus
LIT-1201828