Johnson Controls VFD  Series Installation & Operation Manual
Johnson Controls VFD  Series Installation & Operation Manual

Johnson Controls VFD Series Installation & Operation Manual

Variable frequency drive for d-series (dsv/dsh) air-cooled self-contained units, gen c

Advertisement

Quick Links

INDOOR PACKAGED EQUIPMENT
INSTALLATION & OPERATION
NEW RELEASE
Form 145.13-NO2 (120)
VARIABLE FREQUENCY DRIVE
FOR
D-SERIES (DSV/DSH) AIR-COOLED SELF-CONTAINED UNITS, GEN C
R-410A
Issue Date:
January 22, 2020

Advertisement

Table of Contents
loading

Summary of Contents for Johnson Controls VFD Series

  • Page 1 INDOOR PACKAGED EQUIPMENT INSTALLATION & OPERATION NEW RELEASE Form 145.13-NO2 (120) VARIABLE FREQUENCY DRIVE D-SERIES (DSV/DSH) AIR-COOLED SELF-CONTAINED UNITS, GEN C R-410A Issue Date: January 22, 2020...
  • Page 2 FORM 145.13-NO2 ISSUE DATE: 1/22/2020 IMPORTANT! READ BEFORE PROCEEDING! GENERAL SAFETY GUIDELINES This equipment is a relatively complicated apparatus. which it is situated, as well as severe personal injury or During rigging, installation, operation, maintenance, death to themselves and people at the site. or service, individuals may be exposed to certain com- This document is intended for use by owner-authorized ponents or conditions including, but not limited to:...
  • Page 3 FORM 145.13-NO2 ISSUE DATE: 1/22/2020 CHANGEABILITY OF THIS DOCUMENT In complying with policy for continuous product im- verify whether the equipment has been modified and provement, the information contained in this document if current literature is available from the owner of is subject to change without notice.
  • Page 4 FORM 145.13-NO2 ISSUE DATE: 1/22/2020 VFD NOMENCLATURE 1, 2, 3 4, 5, 6 7, 8, 9, 10, 11 234HE Product Category Design Series VFD = VFD Program A = Current Parameter Set VFD Option Voltage LAC = Low Ambient Condenser 2 = 208-230/3/60 SEC = Smart Equipment Controller 4 = 460/3/60...
  • Page 5: Table Of Contents

    FORM 145.13-NO2 ISSUE DATE: 1/22/2020 TABLE OF CONTENTS SECTION 1 - INSTALLATION ..........................7 Background ..............................7 Factory Shipped ............................... 7 DSV Models ..............................7 DSH Models ..............................8 VAV Units ................................8 Multi-speed Fan Control ........................... 9 VFD Keypad ..............................9 Installation ..............................
  • Page 6 FORM 145.13-NO2 ISSUE DATE: 1/22/2020 THIS PAGE INTENTIONALLY LEFT BLANK.
  • Page 7: Section 1 - Installation

    FORM 145.13-NO2 ISSUE DATE: 1/22/2020 SECTION 1 - INSTALLATION Do not enter Setup mode when powering Do not run the evaporator fan motor be- on the VFD. low 30Hz, as coil freeze-up and nuisance lockouts may occur. The unit is factory set Do not change parameters 4009 and 4011 to minimum 30 Hz output with the excep- for the VAV option on DSH/DSV C-gen...
  • Page 8: Dsh Models

    FORM 145.13-NO2 SECTION 1 - INSTALLATION ISSUE DATE: 1/22/2020 DSH MODELS • Only on 208/230-460 VAC units; not on 575 VAC • 4009 and 4011 are parameters within the The VFD controller on DSH units is factory wired. The ABB VFD drive and are factory set at evaporator fan power conductors are factory wired to 0.5 ”WC.
  • Page 9: Multi-Speed Fan Control

    FORM 145.13-NO2 SECTION 1 - INSTALLATION ISSUE DATE: 1/22/2020 MULTI-SPEED FAN CONTROL VFD FACTORY PROGRAMMED VFD PART #: VFD-SEC-XXXHE-X INDOOR FAN SPEED CONTROL VFD APPLICATION: DATE PROGRAMMED: 05/10/16 DRIVE FACTORY PROGRAMMED NO FIELD PROGRAMMING REQUIRED FOR TECHNICAL SUPPORT, CALL: 877-329-7430 AJAX, CANADA STK-VFD LD20872...
  • Page 10: Installation

    FORM 145.13-NO2 SECTION 1 - INSTALLATION ISSUE DATE: 1/22/2020 INSTALLATION INSTALL GRILLE COVER For units utilizing the VAV option, install a field sup- When the unit is wired and the push-on tubing is con- plied 1/4-inch push-on tube to the return air side of the nected to the transducer, attach the grille cover using unit.
  • Page 11: Section 2 - Operation

    FORM 145.13-NO2 ISSUE DATE: 1/22/2020 SECTION 2 - OPERATION INPUT/OUTPUT DISPLAY In AUTO MODE, the following parameters display on control display: 1. 30–60Hz is the output frequency to the motor. The minimum factory set frequency allowed is 30 Hz. 2. 0.0–Nominal Motor Amps. The maximum amps draw is factory set, and is set to nominal amp draw of motor used.
  • Page 12: Table 1 - Dsh/Dsv Only Factory Parameters For Multi Speed Evaporator Application (Abb Acs320)

    FORM 145.13-NO2 SECTION 2 - OPERATION ISSUE DATE: 1/22/2020 TABLE 1 - DSH/DSV ONLY FACTORY PARAMETERS FOR MULTI SPEED EVAPORATOR APPLICATION - 208/230 AND 460 VAC (ABB ACS320) NAME VALUE UNIT START-UP DATA LANGUAGE ENGLISH APPLIC MACRO HVAC DEFAULT MOTOR NOM VOLT DRIVE DEPENDENT MOTOR NOM CURR DRIVE DEPENDENT...
  • Page 13: Table 2 - Dsh/Dsv Only Factory Parameters For Low Ambient Condenser Application (Abb Acs320)

    FORM 145.13-NO2 SECTION 2 - OPERATION ISSUE DATE: 1/22/2020 TABLE 1 - DSH/DSV ONLY FACTORY PARAMETERS FOR MULTI SPEED EVAPORATOR APPLICATION - 208/230 AND 460 VAC (ABB ACS320) (CONT'D) NAME VALUE UNIT OUTPUT2 UNIT OUTPUT2 MIN OUTPUT2 MAX TABLE 2 - DSH/DSV ONLY FACTORY PARAMETERS FOR LOW AMBIENT CONDENSER APPLICATION 208/230 AND 460 VAC (ABB ACS320) NAME VALUE...
  • Page 14: Table 3 - Dsh/Dsv Only Factory Parameters And Signals For 575V Evaporator Settings (Abb Acs250)

    FORM 145.13-NO2 SECTION 2 - OPERATION ISSUE DATE: 1/22/2020 TABLE 2 - DSV ONLY FACTORY PARAMETERS FOR LOW AMBIENT CONDENSER APPLICATION - 208/230 AND 460 VAC (ABB ACS320) (CONT'D) NAME VALUE UNIT SIGNAL1 MAX OUTPUT1 UNIT SIGNAL2 PARAM PID 1 SETPNT OUTPUT2 DSP FORM DIRECT PROCESS PID SET 1...
  • Page 15: Table 4 - Dsv Only Drive Dependent Parameters Group 99

    FORM 145.13-NO2 SECTION 2 - OPERATION ISSUE DATE: 1/22/2020 TABLE 4 - DSV ONLY DRIVE DEPENDENT PARAMETERS GROUP 99 VFD PROGRAM MOTOR NOMINAL MOTOR NOMINAL VOLTAGE CURRENT FLA SPEED RPM PART # VFD-LAC-233HE-2 208-230/3/60 3.10 1760 VFD-LAC-233HE-4 460/3/60 1.50 VFD-LAC-234HE-2 208-230/3/60 4.50 1.50...
  • Page 16: Vfd Option Schematics

    FORM 145.13-NO2 SECTION 2 - OPERATION ISSUE DATE: 1/22/2020 VFD OPTION SCHEMATICS LD28643 FIGURE 8 - EVAPORATOR VFD LOW VOLTAGE WIRING SCHEMATIC WITH OPTIONAL VAV SENSOR (208/230/460V)
  • Page 17: Figure 9 - Evaporator Vfd Low Voltage Wiring Schematic (575V)

    FORM 145.13-NO2 SECTION 2 - OPERATION ISSUE DATE: 1/22/2020 LD28648 FIGURE 9 - EVAPORATOR VFD LOW VOLTAGE WIRING SCHEMATIC (575V) LD28644 FIGURE 10 - EVAPORATOR HIGH VOLTAGE POWER SCHEMATIC FOR ALL UNITS (208/230/460/575V)
  • Page 18: Figure 11 - Condenser Vfd Low Voltage Wiring Schematic (208/230/460V)

    FORM 145.13-NO2 SECTION 2 - OPERATION ISSUE DATE: 1/22/2020 LD28647 FIGURE 11 - CONDENSER VFD LOW VOLTAGE WIRING SCHEMATIC (208/230/460V) LD28646 FIGURE 12 - CONDENSER VFD HIGH VOLTAGE WIRING SCHEMATIC WITH OPTIONAL MANUAL BYPASS (208/230/460V)
  • Page 19 FORM 145.13-NO2 SECTION 2 - OPERATION ISSUE DATE: 1/22/2020 THIS PAGE INTENTIONALLY LEFT BLANK.
  • Page 20 Subject to change without notice. | Form: 145.13-NO2 (120) | New Release | All rights reserved. The Smart Equipment logo is a trademark of Johnson Controls in the United States and other countries. It is a part of the Johnson Controls product portfolio.