Summary of Contents for Johnson Controls VFD-2DS-234HE-2
Page 1
INDOOR PACKAGED EQUIPMENT INSTALLATION & OPERATION NEW RELEASE Form 145.13-NO1 (1016) VARIABLE FREQUENCY DRIVE D-SERIES (DSV/DSH) AIR-COOLED SELF-CONTAINED UNITS, B STYLE C-SERIES (CSV) WATER-COOLED SELF-CONTAINED UNITS, B STYLE R-410A Issue Date: October 6, 2016...
Page 2
All wiring must be in accor- dance with Johnson Controls’ published specifications and must be performed only by a qualified electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper connections to the controls or application of improper control signals.
Page 3
FORM 145.13-NO1 ISSUE DATE: 10/06/2016 CHANGEABILITY OF THIS DOCUMENT In complying with Johnson Controls’ policy for con- regarding the applicability of these documents, rig- tinuous product improvement, the information con- ging, lifting, and operating/service personnel should tained in this document is subject to change without verify whether the equipment has been modified and notice.
Page 4
LAC = Low Ambient Condenser 5 = 575/3/60 Motor Model Number 234HE = 1.5 HP Motor 235HE = 2.0 HP Motor 236HE = 3.0 HP Motor 237HE = 5.0 HP Motor 238HE = 7.5 HP Motor 239HE = 10.0 HP Motor JOHNSON CONTROLS...
Control wiring for field split applications VFD will control amps draw of the motor and will not needs to be field provided and routed from condenser let the motor draw more than nominal amps. to evaporator. JOHNSON CONTROLS...
SET PARAMETER 4009 & 4011 PRIOR TO START-UP have Discrete 2 Speed Fan Control by default for all units 10 tons or larger FOR TECHNICAL SUPPORT, CALL: 877-329-7430 JOHNSON CONTROLS, AJAX, CANADA STK-VFD DISCRETE 2 SPEED FAN CONTROL LD20871 FIGURE 1 - WARNING LABEL ON UNIT/VFD FOR...
A single keypad can opening, and connect to the positive (HIGH) side fit- be used to program multiple units. If needed, consult ting. with local Johnson Controls sales office to order ad- ditional keypads. JOHNSON CONTROLS...
FIGURE 5 - CONNECTING NEGATIVE AND POSITIVE SIDE FITTINGS Ensure the tubes are secure inside duct and firmly con- nected to transducer fitting, otherwise unit will not op- erate as intended. LD20864 FIGURE 6 - VFD GRILLE COVER JOHNSON CONTROLS...
TABLE 4 - DRIVE DEPENDENT PARAMETERS GROUP 99 (CONT'D) AJAX MOTOR MOTOR MOTOR VFD PROGRAM (BALDOR MOTOR) ABB VFD MODEL # VOLTAGE NOMINAL NOMINAL PART # MODEL # CURRENT FLA SPEED RPM VFD-2DS-234HE-2 ACS320-03U-07A4-2 208-230/3/60 4.50 MTR-234HE (EM3154T) VFD-2DS-234HE-4 ACS320-03U-03A3-4 460/3/60 2.20 1.50 1755 MTR-534HE VFD-2DS-234HE-5...