Setting Parameters List - Omron K7GE-MG User Manual

Insulation resistance monitoring device
Hide thumbs Also See for K7GE-MG:
Table of Contents

Advertisement

A Appendices
A-2 Setting Parameters List
Enter the setting value to use the parameter.
Level
Protect
Initial Setting
Communications
Setting
Note
Highlighted values indicate default settings.
A - 6
Parameter
Characters
name
Setting
wtpt
Change
Protection
Maximum
mxch
Number of
Channels
Alarm Value 1
alm1
Alarm Value 2
alm2
Alarm Polarity
nonc
Trigger Signal
tr-r
Reverse
Motor Stop
mtwt
Waiting Time
Time to Wait to
stwt
Stabilize
Average
avg
Processing
Use Running
age
Time
Protocol
psel
Baud Rate
bps
Data Length
len
Stop Bits
sbit
Parity
prty
Send Wait
sdwt
Time
Setting range
Description
OFF/ON
Use key operations to change
the setting value
Enabled/Disabled
1 to 8
Total number of channels
0.0 to 99.9
Alarm threshold value (warning)
Default value: 20.0
0.0 to 99.9
Alarm threshold value (critical)
Default value: 1.0
n-o/n-c
Alarm output polarity
Normally open/Normally close
OFF/ON
Start measurement when trigger
contact input is OFF/Start
measurement when trigger
contact input is ON
0 to 299 s
Time from trigger input to load
stopping
Default value: 10
0 to 99 s
Time for the measurement value
to stabilize after the Megger
voltage is applied
Default value: 60
OFF/ON
Average processing of
measurement values
None/Yes
OFF/ON
Running time estimation function
Not used/Used
CWF/MOD
Protocol selection
CompoWay/F / Modbus RTU
9.6/19.2/38.4/
Baud rate
57.6 kbps
Default value: 9.6
7/8 bits
Data length
Default value: 7
1/2 bits
Stop bits
Default value: 2
NONE/EVEN/
Parity
ODD
Default value: EVEN
0 to 99 ms
Response wait time from the host
Default value: 20
Insulation Resistance Monitoring Device User's Manual (N224)
Setting
value