2 Procedure
Manual measurement is ended.
•
Press the Manual Measurement Key for 1 second to end
manual measurement, and the K7GE-MG will return to
measurement standby in the Operation Level.
In addition, the measurement will be ended automatically 3
minutes after the start of manual measurement.
Perform manual measurement for the remaining channels as well.
•
Repeat the process to perform manual measurement for the
remaining channels as well, and check the measurement
values.
(5) Starting Operation
Turn ON the load contactor.
•
Make sure the peripheral equipment including loads are
operating correctly.
Turn OFF the load contactor.
•
Automatic measurement is started.
TRIG indicator will light on the measurement step indicator.
The main display part shows the approximate number of
seconds required to complete the measurement, and it will be
counted down.
•
The discharge of electric charge is performed after the time set
in the Motor Stop Waiting Time setting parameter has elapsed.
The measurement step indicator moves to the next step. The
first arrow indicates that the discharge of electric charge is in
progress.
The MEAS indicator on channel 1 of the Probe Unit will light in
measurement operation.
This process always requires 20 seconds.
•
A Megger voltage is applied and it is held for approximately 60
seconds until the measurement value stabilizes.
The measurement step indicator moves to next step. The
second arrow indicates waiting for stability.
•
Sampling is performed. It takes about 1 second.
The measurement step indicator moves to next step. The third
arrow indicates that measurement is in progress.
2 - 8
Insulation Resistance Monitoring Device User's Manual (N224)
MANU
TRIG
FIN
LVL
MEAS
----
1
1 second
CH
MANU
ERR
AGE
TRIG
FIN
LVL
--96
1
CH
MANU
ERR
AGE
CH1 CH2 CH3
TRIG
FIN
LVL
--81
1
CH
MANU
ERR
AGE
CH1 CH2 CH3
TRIG
FIN
LVL
--61
1
CH
MANU
ERR
AGE
CH1 CH2 CH3
TRIG
FIN
LVL
--61
1
CH
CH1 CH2 CH3
MANU
ERR
AGE