Omron K7GE-MG User Manual page 154

Insulation resistance monitoring device
Hide thumbs Also See for K7GE-MG:
Table of Contents

Advertisement

7 Troubleshooting
7-1
Troubleshooting
Check the following table if the K7GE-MG does not perform the expected operation.
No.
When
1
At power ON
2
At power ON
3
At power ON
4
At power ON
7 - 2
Problems
Power supply is unstable,
such as a flickering display.
Sudden alarm output when
attempting to check the setting
parameters.
ERR indicator is
TRIG
FIN
LVL
lit, and 8888 is
8888
displayed.
MANU
ERR
AGE
→ A system
error occurred.
The PWR
indicator is not lit
on some Probe
Units.
Cause
A wire may be
Check again that the
connected to the
wire is securely
release hole in a
connected to the
Push-In Plus terminal
terminal hole. Also
block.
check the other
terminals.
When moving to a level
As an example of a
other than the
countermeasure to this,
Operation Level, the
provide a switch that
ALM 1 and ALM 2
can short-circuit the
output contacts turn
output contacts of the
OFF, regardless of the
ALM 1 and ALM 2, and
setting value of the
use it to short-circuit the
Alarm Polarity setting
contacts during setting
parameter. An external
parameter operations
device may have
and to release the short
judged this to be an
circuit after returning to
alarm.
the Operation Level.
The channel numbers
Check that the channel
of the Probe Units may
numbers of the Probe
be duplicated.
Units are correctly set to
consecutive numbers
starting from 1.
If the channel numbers
It is necessary to
are not duplicated, a
perform repair work.
hardware failure has
Contact your OMRON
occurred.
representative.
The connectors are not
Check the connections
mated properly between
between the Units
the Units.
again.
If there is no
It is necessary to
improvement in
perform repair work.
operation, the Probe
Contact your OMRON
Unit may have a
representative.
hardware failure.
Insulation Resistance Monitoring Device User's Manual (N224)
Correction
Reference
3-4 How to
Connect to
the Push-In
Plus Terminal
Blocks on
page 3-7
4-5 Current
Limiter on
page 4-23
3-3 Setting
the Channel
Number on
page 3-6
-
3-2
Installation on
page 3-3
-