Omron K7GE-MG User Manual page 74

Insulation resistance monitoring device
Hide thumbs Also See for K7GE-MG:
Table of Contents

Advertisement

4 Functions Related to Measurement
Sampling
In this step, the measurement value is confirmed,
and an alarm judgment is performed.
Depending on whether or not average processing
is performed for the measurement values, the
time taken for this step is 0.8 seconds or 6.4
seconds.
Whether or not to perform average processing
can be set by the Average Processing setting
parameter. Refer to 5-9 Average Processing on page 5-19 for the operation method.
The alarm judgment is performed based on the confirmed measurement value, and an alarm is output.
The threshold value used in the alarm judgment can be set by the Alarm Value 1 and Alarm Value 2
setting parameters. Refer to 5-4 Alarm Values 1 and 2 on page 5-9 for the operation method.
If there is another channel to measure, the measurement is performed from the second step "Discharge
of electric charge".
Automatic Measurement Is Ended
This is the state when automatic
measurement of all channels is
complete.
FIN indicator is lit on the
measurement step indicator.
4 - 6
TRIG
FIN
Measurement operation
Measurement value
Measurement
Measurement value confirmation
Alarm output
TRIG
FIN
ON
Trigger signal
Motor stop
standby
Insulation Resistance Monitoring Device User's Manual (N224)
Waiting
Sampling
for stability
0.8 s or 6.4 s
Measurement value
Alarm judgment
ON/OFF
CH3
Discharge of
Discharge of
Waiting for
Sampling
electric charge
electric charge
stability
Measurement end
FIN
indicator is lit