Omron K7GE-MG User Manual page 131

Insulation resistance monitoring device
Hide thumbs Also See for K7GE-MG:
Table of Contents

Advertisement

Details about status information
Variable
Variable
address
name
H'0003
K7GE-MG
Status
Variable
Variable
address
name
H'0005
CH1
Status
Insulation Resistance Monitoring Device User's Manual (N224)
B15
B7
B6
B5
B4
B3
-8
B15
B7
B6
B5
B4
B3
-8
B2
B1
B0
Bit name
Comprehensive
alarm 1
Comprehensive
alarm 2
Operation Level
Automatic
measurement in
progress
Manual
measurement
Running time
-
Trigger input
contacts
-
B2
B1
B0
Bit name
CH1 alarm 1
CH1 Alarm 2
-
CH1 automatic
measurement
CH1
measurement
failed
CH1 automatic
measurement
stopped
-
-
-
6 Remote Monitoring
Description
0: Alarm 1 did not occur in any
channel
1: Alarm 1 occurred in a channel
0: Alarm 2 did not occur in any
channel
1: Alarm 2 occurred in a channel
0: Current level is not Operation
Level
1: Current level is Operation Level
0: No automatic measurement for
any channel
1: Automatic measurement is in
progress for a channel
0: No manual measurement
1: Manual measurement in
progress
0: Running Time Value is less than
100%
1: Running Time Value reached
100%
Not used: Always 0
0: Trigger input terminal external
contacts OFF
1: Trigger input terminal external
contacts ON
Not used: Always 0
Description
0: Alarm 1 did not occur in CH1
1: Alarm 1 occurred in CH1
0: Alarm 2 did not occur in CH1
1: Alarm 2 occurred in CH1
Not used: Always 0
0: No automatic measurement in
CH1
1: Automatic measurement in
progress in CH1
0: Measurement did not fail in
CH1
1: Measurement failed in CH1
0: Automatic measurement not
stopped in CH1
1: Automatic measurement
stopped (trigger released) in
CH1
Not used: Always 0
Not used: Always 0
Not used: Always 0
6 - 7
6